Main
Range
ClimaSys
Product Name
ClimaSys CV
type of filter
Standard
Complementary
[in] rated current
0.35 A 50 Hz
0.32 A 60 Hz
Handle front plate colour
268 mm external:
Product or component type
Fan
[us] rated supply voltage
75...126 V
Device composition
1 axial motor
2 protective grille: on the front and rear surfaces
1 filter: front of axial motor
1 outlet grille: front
1 cut-out template
1 power cord
Bearing type
Ball
Connections - terminals
Faston connector
Flow rate
Free flow rate with standard filter: 300 m3/h at 50 Hz
Free flow rate with standard filter: 350 m3/h at 60 Hz
Cut-out dimensions
223 x 223 mm
Condition of use
Flow rates depends on the work point, see ProClima software
Surrounding environment must be relatively clean
Outside temperature must be 5 °C lower than inside temperature
Filter must be cleaned and replaced regularly
Overfrequent filter replacement should be avoided
Material
Outlet grille: injected thermoplastic (ASA PC)
width (w)
248 mm external:
Colour
Outlet grille: grey (RAL 7035)
maximum pressure
158 Pa flow rate 0 m³/h
Net weight
1.3 kg
absorbed power
36 W 50 Hz
36 W 60 Hz
depth
116 mm external:
Noise level < at
55…56 dB
input voltage
115 V 50/60 Hz
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP54
ambient air temperature for operation
-10…70 °C