Main
Cooling power
380 W 50/60 Hz L35-L35
240 W 50/60 Hz L35-L50
Range
ClimaSys
Mounting type
Side
Product Name
CU
temperature setting range
20…55 °C at 50 Hz
20…50 °C at 60 Hz
type of filter
Optional external circuit filter
Complementary
[in] rated current
1.6 A
Control type
Electronic controller
Product certifications
CE
Handle front plate colour
460 mm
Product or component type
Cooling unit
Cooling gas type
R134a (0.16 kg)
inrush current
6 A
Flow rate
Internal circuit: 280 m3/h at 50/60 Hz
External circuit: 280 m3/h at 50/60 Hz
noise level
60 dB conforming to EN/ISO 3746
Energy efficiency ratio
1.4
Material
Steel
width (w)
285 mm
Colour
Grey (RAL 7035)
Mounting mode
By screws
Net weight
17 kg
Pressure
26 bar
depth
180 mm
Power consumption in w
280 W at 50/60 Hz, L35-L35
330 W at 50/60 Hz, L35-L50
Type of installation
Indoor
input voltage
230 V 50/60 Hz
Network number of phases
1 phase
Product destination
For enclosure
Protection type
Thermal protection: T 4 A
Short-circuit protection (magnetic):
Environment
Directives
2006/95/EC - low voltage directive
2004/108/EC - electromagnetic compatibility
2006/42/EC - machinery
ip degree of protection
IP55 conforming to IEC 60529 (on the internal circuit)
IP34 conforming to IEC 60529 (on the external circuit)
ambient air temperature for operation
20…46 °C inside the enclosure:
55 °C maximum:
20…55 °C at 50 Hz outside the enclosure:
20…50 °C at 60 Hz outside the enclosure:
standards
EN 378
EN 60335-2-40
EN 60204-1
EN/ISO 12100
EN 60335-1