Main
Cooling power
1550 W 50/60 Hz L35-L35
1200 W 50/60 Hz L35-L50
Range
ClimaSys
Mounting type
Roof of enclosure
Product Name
CU
temperature setting range
20…55 °C at 50 Hz
20…50 °C at 60 Hz
type of filter
Optional external circuit filter
Complementary
[in] rated current
4.5 A
Control type
Electronic controller
Product certifications
CE
Handle front plate colour
415 mm
Product or component type
Cooling unit
Cooling gas type
R134a (0.54 kg)
inrush current
18 A
Flow rate
Internal circuit: 860 m3/h at 50/60 Hz
External circuit: 1820 m3/h at 50/60 Hz
noise level
65 dB conforming to EN/ISO 3746
Energy efficiency ratio
1.9
Material
Steel
width (w)
567 mm
Colour
Grey (RAL 7035)
Mounting mode
By screws
Net weight
44 kg
Pressure
25 bar
depth
401 mm
Power consumption in w
810 W at 50/60 Hz, L35-L35
930 W at 50/60 Hz, L35-L50
Type of installation
Indoor
input voltage
230 V 50/60 Hz
Network number of phases
1 phase
Product destination
For enclosure
Protection type
Thermal protection: T 10 A
Short-circuit protection (magnetic):
Environment
Directives
2004/108/EC - electromagnetic compatibility
2006/95/EC - low voltage directive
2006/42/EC - machinery
ip degree of protection
IP34 conforming to IEC 60529 (on the external circuit)
IP54 conforming to IEC 60529 (on the internal circuit)
ambient air temperature for operation
20…46 °C inside the enclosure:
55 °C maximum:
20…55 °C at 50 Hz outside the enclosure:
20…50 °C at 60 Hz outside the enclosure:
standards
EN 60335-1
EN/ISO 12100
EN 378
EN 60204-1
EN 60335-2-40