SPECIFICATIONS
Main
Device short name PM5561
Measurement current 50…10000 mA
Range PowerLogic
Product Name PowerLogic PM5000
Measurement voltage 20…400 V AC 45...65 Hz between phase and neutral
20…828 V AC 45...65 Hz between phases
Complementary
power quality analysis up to the 63rd harmonic
[in] rated current 5 A
1 A
maximum power consumption in va 16 VA at 480 V
memory capacity 1.1 MB
Product certifications CE conforming to IEC 61010-1
CULus conforming to UL 61010-1
MID conforming to EN 50470-1
MID conforming to EN 50470-3
Communication port support RS485
ETHERNET
Handle front plate colour 96 mm
Product or component type Power meter
accuracy class Class 0.2S active energy conforming to IEC 62053-22
Connections - terminals Voltage circuit: screw terminal block4
Control circuit: screw terminal block2
Current transformer: screw terminal block6
RS485 link: screw terminal block4
Digital input: screw terminal block8
Digital output: screw terminal block4
Ethernet network: RJ45 connector2
Device application Multi-tariff
WAGES metering
Gateway
Power monitoring
type of measurement Current
Voltage
Frequency
Power factor
Energy
Active and reactive power
Analogue input type Voltage (impedance 5 MOhm)
Current (impedance <= 0.3 mOhm)
communication gateway Ethernet/serial
Data recording Maintenance logs
Data logs
Alarm logs
Event logs
Min/max of instantaneous values
Time stamping
information displayed Tariff (8)
width (w) 96 mm
network frequency 60 Hz
50 Hz
number of outputs 2 digital
Mounting mode Flush-mounted
Net weight 450 g
Ethernet service SNMP-Traps
SNTP client
frequency measurement range 45…65 Hz
measurement accuracy Apparent power +/- 0.5 %
Frequency +/- 0.05 %
Active energy +/- 0.2 %
Reactive energy +/- 1 %
Active power +/- 0.2 %
Voltage +/- 0.1 %
Power factor +/- 0.005
Current +/- 0.15 %
Reactive power +/- 1 %
communication port protocol Modbus RTU and ASCII at 9.6, 19.2 and 38.4 kbauds even/odd or none - 2 wires, insulation 2500 V
JBUS
Modbus TCP/IP at 10/100 Mbit/s, insulation 2500 V
Ethernet Modbus TCP/IP daisy chain
BACnet IP
DNP3 over ethernet
Display type Backlit LCD
Mounting support Framework
depth 72 mm
Network type 3P
3P + N
1P + N
Number of inputs 4 digital
Pollution degree 2
sampling rate 128 samples/cycle
display resolution 128 x 128 pixels
Metering type Measured neutral current
Calculated ground current
supply voltage 100...300 V DC
90...528 V AC 45...65 Hz
Ride-through time 35 ms 120 V AC typical
129 ms 230 V AC typical
50 ms 125 V DC typical
Web services Alarm notification by e-mail
Web server
Diagnostic via predefined web pages
Real time viewing of data
Environment
Ambient air temp for storage/transportation -40…85 °C
ip degree of protection IP54 display: conforming to IEC 60529
IP30 rear: conforming to IEC 60529
operating altitude <= 3000 m
ambient air temperature for operation -25…70 °C
electromagnetic compatibility Limits for harmonic current emissions class A conforming to IEC 61000-3-2
Conducted RF disturbances level 3 conforming to IEC 61000-4-6
Magnetic field at power frequency level 4 conforming to IEC 61000-4-8
Conducted and radiated emissions class B conforming to EN 55022
Limitation of voltage changes, voltage fluctuations and flicker in low-voltage conforming to IEC 61000-3-3
Electrostatic discharge - test level: 8 kV level 4 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
Surge immunity test level 4 conforming to IEC 61000-4-5
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
standards IEC 60529
EN 50470-1
UL 61010-1
IEC 62053-24
EN 50470-3
IEC 62053-22
IEC 61557-12
ANSI C12.20
relative humidity 5…95 % at 50 °C non-condensing