Main
Device short name
PM5350
Measurement current
5…9000 mA
Range
PowerLogic
Product Name
PowerLogic PM5350
Measurement voltage
35…760 V AC 45...65 Hz phase to phase
20…400 V AC phase to neutral
Complementary
power quality analysis
total demand distortion
total harmonic distortion
[in] rated current
5 A
1 A
maximum power consumption in va
11.9 VA
Product certifications
CE
CULus
Communication port support
Terminal block: RS485
Handle front plate colour
96 mm
Product or component type
Power meter
accuracy class
Class 0.5S active energy conforming to IEC 62053-22
Class 0.5 active energy conforming to IEC 61557-12
Class 3 reactive energy conforming to IEC 62053-23
Class 2 reactive energy conforming to IEC 61557-12
Class 0.5 power conforming to IEC 61557-12
Connections - terminals
Voltage circuit: screw terminal block4
Control circuit: screw terminal block2
Current transformer: screw terminal block6
Input/output circuit: screw terminal block6
Relay output: screw terminal block4
Ethernet network: RJ45 connector
Device application
Power monitoring
type of measurement
Current
Voltage
Frequency
Power factor
Energy
Phase angle
Apparent power
Active power
Reactive power
Analogue input type
Current 0.05...9 A (impedance <= 0.3 mOhm)
Voltage (impedance 10 MOhm)
Data recording
Min/max of instantaneous values
Alarms
information displayed
Tariff (4)
width (w)
96 mm
network frequency
50 Hz
60 Hz
number of outputs
2 relay
Mounting mode
Flush-mounted
Net weight
0.25 kg
frequency measurement range
45…70 Hz
measurement accuracy
Current +/- 0.5 %
Voltage +/- 0.5 %
Frequency +/- 0.05 %
Power factor +/- 0.5
Active energy +/- 0.5 %
Reactive energy +/- 2 %
Active power +/- 0.5 %
Apparent power +/- 0.5 %
Apparent energy +/- 0.5 %
Reactive power +/- 2 %
communication port protocol
JBUS
Modbus RTU and ASCII at 9.6, 19.2 and 38.4 kbauds
Display type
Monochrome graphic LCD
depth
44 mm
Network type
1P + N
3P + N
3P
Number of inputs
4 digital
Pollution degree
2
Type of installation
Indoor installation
sampling rate
32 samples/cycle
display resolution
6 lines
supply voltage
90...450 V AC 45...65 Hz
100...300 V DC
Ride-through time
100 ms 120 V AC typical
400 ms 230 V AC typical
50 ms 125 V DC typical
Environment
Ambient air temp for storage/transportation
-40…85 °C
ip degree of protection
IP30 rear: conforming to IEC 60529
IP54 display: conforming to IEC 60529
operating altitude
<= 3000 m
ambient air temperature for operation
-25…70 °C meter
-20…70 °C display
-25…-20 °C (with reduced performance) display
electromagnetic compatibility
Limitation of voltage changes, voltage fluctuations and flicker in low-voltage conforming to IEC 61000-3-3
Electrostatic discharge conforming to IEC 61000-4-2
Susceptibility to electromagnetic fields conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test conforming to IEC 61000-4-4
1.2/50 µs shock waves immunity test conforming to IEC 61000-4-5
Conducted RF disturbances conforming to IEC 61000-4-6
Immunity to impulse waves conforming to IEC 61000-4-12
Conducted and radiated emissions class A conforming to EN 55011
Limits for harmonic current emissions conforming to IEC 61000-3-2
overvoltage category
III
standards
IEC 61010-1
relative humidity
5…95 % at 50 °C non-condensing