Main
Device short name
PM5340
Measurement current
5…9000 mA
Range
PowerLogic
Product Name
PowerLogic PM5000
Measurement voltage
35…760 V AC 45...65 Hz between phases
20…400 V AC 45...65 Hz between phase and neutral
Complementary
power quality analysis
up to the 31st harmonic
[in] rated current
5 A
1 A
maximum power consumption in va
11.9 VA at 415 V
memory capacity
256 kB
Product certifications
CE conforming to IEC 61010-1
CULus conforming to UL 61010-1
Communication port support
ETHERNET
Handle front plate colour
96 mm
Product or component type
Power meter
accuracy class
Class 0.5S active energy conforming to IEC 62053-22
Connections - terminals
Voltage circuit: screw terminal block4
Control circuit: screw terminal block2
Current transformer: screw terminal block6
Input/output circuit: screw terminal block6
Relay output: screw terminal block4
Ethernet network: RJ45 connector
Device application
Multi-tariff
Power monitoring
type of measurement
Current
Voltage
Frequency
Power factor
Energy
Active and reactive power
Analogue input type
Voltage (impedance 10 MOhm)
Current (impedance <= 0.3 mOhm)
Data recording
Data logs
Alarm logs
Time stamping
Event logs
Min/max of instantaneous values
Maintenance logs
information displayed
Tariff (4)
width (w)
96 mm
network frequency
60 Hz
50 Hz
number of outputs
2 relay
2 digital
Mounting mode
Flush-mounted
Net weight
430 g
frequency measurement range
45…65 Hz
measurement accuracy
Active energy +/- 0.5 %
Reactive energy +/- 2 %
Active power +/- 0.5 %
Apparent power +/- 0.5 %
Frequency +/- 0.05 %
Power factor +/- 0.5
Current +/- 0.5 %
Voltage +/- 0.5 %
Apparent energy +/- 0.5 %
Reactive power +/- 2 %
communication port protocol
Modbus TCP/IP at 10/100 Mbit/s, insulation 2500 V
BACnet IP
Display type
Monochrome graphic LCD
Mounting support
Framework
depth
72 mm
Network type
3P
1P + N
3P + N
Number of inputs
2 digital
Pollution degree
2
sampling rate
64 samples/cycle
display resolution
128 x 128 pixels
supply voltage
90...450 V AC 45...65 Hz
100...300 V DC
Ride-through time
100 ms 120 V AC typical
400 ms 230 V AC typical
50 ms 125 V DC typical
Environment
Ambient air temp for storage/transportation
-40…85 °C
ip degree of protection
IP51 display: conforming to IEC 60529
IP30 rear: conforming to IEC 60529
operating altitude
<= 3000 m
ambient air temperature for operation
-25…70 °C meter
-20…70 °C display
-25…-20 °C (with reduced performance) display
electromagnetic compatibility
Limits for harmonic current emissions class A conforming to IEC 61000-3-2
Electrostatic discharge level 4 conforming to IEC 61000-4-2
Conducted RF disturbances level 3 conforming to IEC 61000-4-6
Magnetic field at power frequency level 4 conforming to IEC 61000-4-8
Conducted and radiated emissions class B conforming to EN 55022
standards
EN 50470-1
IEC 62053-24
IEC 60529
UL 61010-1
IEC 62053-22
EN 50470-3
IEC 61557-12
relative humidity
5…95 % at 50 °C non-condensing