Main
Device short name
PM3200
Measurement current
0.05…6 A
0.02…1.2 A
Range
PowerLogic
Product Name
PowerLogic PM3000
Measurement voltage
50…330 V AC 45...65 Hz direct
50…330 V AC 45...65 Hz phase to neutral
80…570 V AC 45...65 Hz direct
80…570 V AC 45...65 Hz phase to phase
570…999000 V AC 45...65 Hz with external VT
Complementary
power quality analysis
up to the 15th harmonic
[in] rated current
5 A
1 A
Product certifications
CE conforming to IEC 61010-1 (safety)
CE conforming to EN 61557-12 (power monitor)
CE conforming to EN/IEC 61326-1 (EMC)
UKCA conforming to BS EN 61010-1 (safety)
UKCA conforming to BS EN 61557-12 (power monitor)
UKCA conforming to BS EN 61326-1 (EMC)
CULus conforming to EN 61010-1 (safety)
CULus conforming to UL 61010-1 (safety)
EAC (sub-meter)
RCM
Communication port support
-
Handle front plate colour
95 mm
Product or component type
Power meter
accuracy class
Class 0.5S active energy conforming to IEC 62053-22
Class 1 active energy conforming to IEC 62053-21
Class 2 reactive energy conforming to IEC 62053-23
Class C active energy conforming to EN 50470-3
Device application
Multi-tariff
Sub billing
Power monitoring
type of measurement
Active and reactive power
Apparent power
Current
Voltage
Energy
Power factor
Frequency
Analogue input type
Current 0...5 A
Current 0...1 A
Data recording
Min/max of instantaneous values
information displayed
Tariff (4)
width (w)
90 mm
network frequency
50 Hz
60 Hz
Mounting mode
Clip-on
Net weight
0.26 kg
frequency measurement range
45…65 Hz
measurement accuracy
Current 0.3 % 0.5...6 A
Current 0.5 % 0.1...1.2 A
Voltage 0.3 % 50...330 V
Voltage 0.3 % 80...570 V
communication port protocol
-
Display type
Backlit LCD
Mounting support
DIN rail
depth
70 mm
Network type
3P + N
3P
1P + N
Pollution degree
2
Power consumption in va
5 VA
sampling rate
32 samples/cycle
display resolution
128 x 96 pixels
supply voltage
100...277 V AC 45...65 Hz
173...480 V AC 45...65 Hz
100...300 V DC
Environment
Ambient air temp for storage/transportation
-40…85 °C
ip degree of protection
IP40 front panel: conforming to IEC 60529
IP20 body: conforming to IEC 60529
operating altitude
< 3000 m
ambient air temperature for operation
-25…70 °C
electromagnetic compatibility
Electrostatic discharge level 4 conforming to IEC 61000-4-2
Susceptibility to electromagnetic fields level 3 conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
Surge immunity test level 4 conforming to IEC 61000-4-5
Conducted RF disturbances level 3 conforming to IEC 61000-4-6
Magnetic field at power frequency - test level: 0.5 mT conforming to IEC 61000-4-8
Conducted and radiated emissions class B conforming to EN 55022
overvoltage category
III
standards
BS EN 61557-12
IEC 61557-12
EN 61557-12
BS EN 61326-1
IEC 61326-1
EN 61326-1
BS EN 62052-11
IEC 62052-11
EN 62052-11
BS EN 62053-21
IEC 62053-21
EN 62053-21
BS EN 62053-22
IEC 62053-22
EN 62052-22
BS EN 62053-23
IEC 62053-23
EN 62052-23
BS EN 61010-1
EN 61010-1
IEC 61010-1
UL 61010-1
BS EN 61010-2-30
IEC 61010-2-30
EN 61010-2-30
UL 61010-2-30
ANSI C12.20
relative humidity
5…95 % at 50 °C