Complementary
electrical insulation class
Class III conforming to EN/IEC 62052-11
power quality analysis
EN 50160 compliance checking
conforming to IEEE 519 harmonic limit
conforming to IEC 61000-4-30: class A compliance reporting
conforming to IEEE 519 compliance reporting
waveform capture
total demand distortion
total harmonic distortion
up to the 63rd harmonic
up to the 127th harmonic with software
disturbance direction detection
dip, swell and transient
half cycle data acquisition
high-speed transient capture
coincidence disturbance waveform capture
transient detection (100 ns)
[in] rated current
1 A
5 A
maximum power consumption in va
80 VA at 480 V AC
memory capacity
2 GB
Communication port support
RS485 2 removable screw terminal block
Handle front plate colour
160 mm
Product or component type
Energy and power quality meter
[us] rated supply voltage
90...480 V AC 45...66 Hz +/- 10 %
90...120 V AC 400 Hz +/- 10 %
110...480 V DC +/- 15 %
accuracy class
Class 0.1S active energy conforming to IEC 62053-22
Class 0.1 active energy conforming to IEC 61557-12
Class 0.1 active energy conforming to ANSI C12.20
Class 0.5S reactive energy conforming to IEC 62053-24
Class 0.1 current conforming to IEC 61557-12
Class 0.1 voltage conforming to IEC 61557-12
Class 0.1 active power conforming to IEC 61557-12
Class 0.5 power factor conforming to IEC 61557-12
Device application
Power monitoring
WAGES metering
Net metering
Medium voltage
High voltage
Installation category
III
type of measurement
Voltage sags and swells
Current sags and swells
Voltage
Current
Frequency
Active and reactive power total
Apparent power total
Active and reactive power per phase
Apparent power per phase
Power factor total
Power factor per phase
Active and reactive energy
Apparent energy
Harmonic distorsion (I THD & U THD)
communication gateway
Ethernet/serial
cybersecurity
Syslog protocol support
Robust security logs
Port hardening
Enable/disable communication ports
Hardware metrology lock
Data recording
Time stamping
Min/max of instantaneous values
User-definable data logs
Continuous logging or snapshot
Trending/forecasting
Event logs
Alarm logs
Configuration change
Power outage
User login/logout
Data logs
GPS synchronisation
Sequence of event recording
width (w)
160 mm
network frequency
50 Hz
60 Hz
number of outputs
4 digital
2 form C relay output
input type
Voltage (impedance 5 MOhm)
External CT (impedance 0.3 mOhm)5 x
Time synchronisation protocol
GPS
IRIG-B
NTP
SNTP
PTP
Net weight
1.5 kg
Ethernet service
DHCP client
Device Profile Web Services (DPWS)
Rapid Scanning Tree Protocol (RSTP)
FTP/HTTP/HTTPS
Communication service
Compliant reports
Power quality summary
Energy report
EcoStruxure Power Events Analysis
SMTP e-mail notification
SNMP
frequency measurement range
20…450 Hz
measurement accuracy
Voltage +/- 0.1 %
Current +/- 0.1 %
communication port protocol
Modbus RTU at 2400...115200 bps - 2-wire
ION at 2400...115200 bps - 2-wire
DNP3 at 2400...115200 bps - 2-wire
Modbus TCP at 10/100 Mbit/s
ION TCP at 10/100 Mbit/s
DNP3 TCP at 10/100 Mbit/s
IEC 61850
Ethernet Modbus TCP/IP daisy chain at 10/100 Mbit/s
DHCP
DNS
DLMS
Display type
Remote LCD display
Colour touchscreen
Mounting support
DIN rail meter device
Door cut-out remote display
depth
135.3 mm
Network type
3P + N + E
Number of inputs
8 digital 30 V AC/60 V DC
Power consumption in va
38 VA at 480 V AC
sampling rate
1024 samples/cycle
display resolution
800 x 480 pixels
port ethernet
10/100BASE-TX 2 RJ45
Tamperproof of settings
Protected by sealable cover
Isolation voltage
III400…690 V conforming to EN 61010-1:ed. 3
III347…600 V conforming to UL 61010-1:ed. 3
III347…600 V conforming to CSA C22.2 No 61010-1:ed. 3
Provided equipment
Remote display
Remote display adapter
Mounting instructions
Mounting hardware
Metering type
Demand current I1, I2, I3, I4, I5
Peak demand currents
Demand power P, Q, S
Peak demand power PM, QM, SM
Calculated active and reactive energy (+/- W.h, +/- VAR.h)
Ride-through time
100 ms 6 cycles at 60 Hz 120 V AC typical
400 ms 24 cycles at 60 Hz 240 V AC typical
1200 ms 72 cycles at 60 Hz 480 V AC typical
Web services
Viewing of captured waveform
Web page
Pass/fail report for IEEE 519
Pass/fail report for EN 50160
ITIC (CBEMA) curve
SEMI curve
NEMA motor derating curve
Alarm notification by e-mail
TLS 1.2
Push historical data via mail
Environment
Ambient air temp for storage/transportation
-40…85 °C
ip degree of protection
IP65 front:
IP30 rear:
operating altitude
0...3000 m
ambient air temperature for operation
-25…70 °C
electromagnetic compatibility
EMC immunity conforming to IEC 62052-11
EMC immunity conforming to IEC 61326-1
EMC immunity conforming to IEC 61000-6-5
Electrostatic discharge immunity test conforming to IEC 61000-4-2
Immunity to radiated fields conforming to IEC 61000-4-3
Immunity to fast transients conforming to IEC 61000-4-4
Surge immunity test conforming to IEC 61000-4-5
Immunity to conducted disturbances conforming to IEC 61000-4-6
Immunity to magnetic fields at network frequency conforming to IEC 61000-4-8
Immunity to conducted disturbances - test level: 2...150 kHz conforming to CLC/TR 50579
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
Immunity to impulse waves conforming to IEC 61000-4-12
Conducted and radiated emissions conforming to EN 55011
Conducted and radiated emissions class B conforming to EN 55032
Conducted and radiated emissions class B conforming to FCC part 15
Conducted and radiated emissions class B conforming to ICES-003
Surge withstand conforming to ANSI C37.90.1
Surge withstand conforming to IEEE C37.90.1
standards
ANSI C12.20
ANSI C37.90.1
IEC 61000-4-15
IEC 61000-4-30
IEC 61010-1
IEC 61326-1
IEC 61557-12
IEC 61850
IEC 62052-11
IEC 62052-31
IEC 62053-22
IEC 62053-23
IEC 62053-24
IEC 62586
UL 61010-1
quality labels
ISO 9001
ISO 14000
relative humidity
5…95 %