Main
Device short name
DM6200
Measurement current
5 A
1 A
Measurement voltage
80…480 V AC phase to phase
Complementary
maximum power consumption in va
3 VA at 240 V AC
Product certifications
CE
Communication port support
Terminal block: RS485
Handle front plate colour
96 mm
Product or component type
Multimeter
[us] rated supply voltage
44...277 V AC 50/60 Hz
44...277 V DC
Device application
Equipment monitoring
Power monitoring
Preventive maintenance
type of measurement
Current
Voltage
Frequency
Power factor
Phase unbalance
Phase angle
RPM
Analogue input type
Current 0.05...6 A (impedance <= 0.1 Ohm)
width (w)
96 mm
network frequency
45...65 Hz
Mounting mode
Flush-mounted
Net weight
0.4 kg
measurement accuracy
Frequency 0.1 %
Power factor 1 %
Voltage 1 % 46...277 V
Current 1 % 0.05...6 A
communication port protocol
Modbus
Display type
LED indicator
depth
80 mm
Pollution degree
2
Type of installation
Indoor installation
sampling rate
20 samples/cycle
Transmission rate
19.2 kbauds
Environment
Ambient air temp for storage/transportation
-25…70 °C
ip degree of protection
IP40 back:
IP51 front face:
operating altitude
0...2000 m
Range of product
PowerLogic
ambient air temperature for operation
-10…60 °C
electromagnetic compatibility
Electrostatic discharge immunity test: , conforming to IEC 61000-4-2
Susceptibility to electromagnetic fields: , conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test: , conforming to IEC 61000-4-4
1.2/50 µs shock waves immunity test: , conforming to IEC 61000-4-5
Conducted RF disturbances: , conforming to IEC 61000-4-6
Immunity to impulse waves: , conforming to IEC 61000-4-12
Conducted and radiated emissions: , A, conforming to CISPR 11
Immunity to microbreaks and voltage drops: , conforming to IEC 61000-4-11
overvoltage category
III
standards
UL 508
IEC 61010
relative humidity
95 %