Main
Accessory category
Measurement accessory
Measurement current
50…5000 A
Range
PowerLogic
Complementary
range compatibility
Acti 9 (Acti9 iEM3000) iEM3555
Acti 9 (Acti9 iEM3000) iEM3565
PowerLogic (PowerLogic EM4200) EM4235
PowerLogic (PowerLogic EM4200) EM4236
PowerLogic (PowerLogic EM3500) EM3502A
PowerLogic (PowerLogic EM3500) EM3550A
PowerLogic (PowerLogic EM3500) EM3555A
PowerLogic (PowerLogic EM3500) EM3560A
PowerLogic (PowerLogic EM3500) EM3561A
Product certifications
UL recognized
CE
cURus
Handle front plate colour
300 mm opened:
Product or component type
Current transducer
thickness
8 mm
diameter
Closed: 96 mm
Installation category
IV
network frequency
50 Hz
frequency measurement range
50…1500 Hz
measurement accuracy
1 %
current transformer type
Flexible core
Pollution degree
2
electrical connection
Flying lead: 2.4 m600 V
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP67
ambient air temperature for operation
-15…60 °C
standards
EN 61010-2-032
UL 61010-2-032
UL 61010-1
EN 61010-1
ANSI/IEEE C57.13
relative humidity
0…95 %