Complementary
air humidity protection
for all climates
bottom connection alignement for modular devices
Aligned terminal
concurrently switching n-neutral
No
connection cross section of access and exit with screws, for flexible conductor
1 / 25 mm²
connection cross-sect. flexible conductor
1 / 25mm²
correction factor of magnetic tripping with 100 hz
1.1
correction factor of rating current for 2 devices placed side-by-side
1
depth of installed product
70 mm
electric endurance in number of cycles
4000
power loss per pole at in
1.3 W
rating current -10°c
2.5 A
search words
Circuit breaker;Machine;Built-in machine;Built-in device;Installation machine;Rail mounted device;Automatic cutout;Controller circuit-breaker;Built-in distribution unit;Automatic plug-in fuse
[in] rated current
2 A
breaking capacity on 1 pole for it 400v nf 60947-2
3 kA
connection cross-sect. rigid cable
1 / 35mm²
correction factor of magnetic tripping with 200 hz
1.2
correction factor of rating current for 3 devices placed side-by-side
0.95
degree of pollution according to iec 60664 / iec 60947-2
2
height of installed product
83 mm
magnetic regulating currrent
5 / 10 In
number of mechanical operations
20000
rating current -15°c
2.6 A
top connection alignement for modular devices
Aligned terminal
total power loss under in
1.3 W
class of energy limitation i²t
3
correction factor of magnetic tripping with 400 hz
1.5
correction factor of rating current for 4 and 5 devices placed side-by-side
0.9
min/maxi threshold value of the ac thermal operation
1.13 / 1.45 In
rating current -20°c
2.6 A
type of connection
with screw
width of installed product
17.5 mm
connection cross-section of input and output with screws, for massive conductors
1 / 35 mm²
correction factor of magnetic tripping with 60 hz
1
correction factor of rating current for 6 devices placed side-by-side
0.85
min/maxi threshold value of the dc magnetic operation
7 / 15 In
rating current -25°c
2.7 A
storage/transport temperature
-25…80 °C
tightening torque
2,8Nm
type of bottom connection for modular devices
BIconnect
min/maxi threshold value of the dc thermal operation
1.13 / 1.45 In
rated ultimate short-circuit breaking capacity icu under 230v ac iec 60947-2
10 kA
rating current -5°c
2.5 A
Rated insulation voltage
500 V
rated ultimate short-circuit breaking capacity icu under 240v ac iec 60947-2
10 kA
rating current 0°c
2.4 A
type of top connection for modular devices
with screw
rated service breaking capacity ics ac according iec 60898-1
6 kA
rating current 10°c
2.3 A
rated short circuit breaking capacity icn under 230v ac according iec60898-1
6 kA
rating current 15°c
2.2 A
rating current 20°c
2.1 A
rating current 25°c
2.1 A
rating current 30°c
2 A
rating current 35°c
1.9 A
rating current 40°c
1.9 A
rating current 45°c
1.8 A
rating current 50°c
1.7 A
rating current 55°c
1.6 A
rating current 5°c
2.3 A
frequency
50 to 60 Hz
rating current 60°c
1.5 A
rating current 65°c
1.4 A
rating current 70°c
1.3 A
rated impulse withstand voltage
4000 V
Poles description
1 P