Complementary
bottom connection alignement for modular devices
Aligned terminal
can be accessorized
No
concurrently switching n-neutral
No
connection cross-section at output with screw, for flexible conductor
1 / 25 mm²
correction factor of rating current for 2 devices placed side-by-side
1
depth of installed product
70 mm
electric endurance in number of cycles
4000
max operating voltage
415 V
maximum power loss per pole according to the product standard
3 W
power loss per pole at in
1.63 W
rating current -10°c
12.54 A
search words
Miniature circuit breaker;mini automatic
[in] rated current
10 A
correction factor of rating current for 3 devices placed side-by-side
0.95
degree of pollution according to iec 60664 / iec 60947-2
2
magnetic regulating currrent
5 / 10 In
number of mechanical operations
20000
rating current -15°c
12.8 A
top connection alignement for modular devices
Aligned terminal
class of energy limitation i²t
3
correction factor of rating current for 4 and 5 devices placed side-by-side
0.9
min/maxi threshold value of the ac thermal operation
1.13 / 1.45 In
rating current -20°c
13.1 A
type of connection
with screw
width of installed product
17.5 mm
connection cross-section at output with screw, for massive conductor
1 / 35 mm²
correction factor of rating current for 6 devices placed side-by-side
0.85
rating current -25°c
13.4 A
storage/transport temperature
-25…80 °C
tightening torque
2,8Nm
type of bottom connection for modular devices
BIconnect
connection cross-section for rigid conductor, upstream terminals with screws
1 / 35 mm²
rated short circuit breaking capacity icn under 400v ac according iec60898-1
6 kA
rating current -5°c
12.21 A
connection cross-section of the access with screws, with flexible conductor
1 / 25 mm²
Rated insulation voltage
500 V
rating current 0°c
11.91 A
type of top connection for modular devices
with screw
rating current 10°c
11.31 A
rated short circuit breaking capacity icn under 230v ac according iec60898-1
6 kA
rating current 15°c
11.01 A
Fixing mode
DIN rail type O (symmetrical)
rating current 20°c
10.72 A
rating current 25°c
10.42 A
rating current 30°c
10 A
rating current 35°c
9.82 A
rating current 40°c
9.52 A
rating current 45°c
9.22 A
rating current 50°c
9 A
rating current 55°c
8.63 A
rating current 5°c
11.61 A
rating current 60°c
8.33 A
rating current 65°c
8.03 A
rating current 70°c
7.73 A
rated impulse withstand voltage
4000 V
Poles description
1 P