Additional Information
curve
C
Main
Range
Multi9
Number of protected poles
2
Product Name
C60
Trip unit technology
Thermal-magnetic
[ui] rated insulation voltage
500 V DC conforming to EN/IEC 60947-2
Complementary
9 mm pitches
4
[in] rated current
10 A at 25 °C
[ue] rated operational voltage
220 V DC
250 V DC
440 V DC
500 V DC
[ics] rated service breaking capacity
15 kA 75 % conforming to EN/IEC 60947-2 - 220 V DC
15 kA 75 % conforming to EN/IEC 60947-2 - 250 V DC
7.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V DC
4.5 kA 75 % conforming to EN/IEC 60947-2 - 500 V DC
Control type
Toggle
Product certifications
CE
Handle front plate colour
81 mm
Product or component type
Miniature circuit-breaker
tightening torque
2.5 N.m top or bottom
[uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-2
Comb busbar and distribution block compatibility
YES
Connections - terminals
Tunnel type terminals (top or bottom) 1…25 mm² rigid stranded
Tunnel type terminals (top or bottom) 1…16 mm² flexible
Tunnel type terminals (top or bottom) 1…16 mm²
Locking options description
Padlocking device
Contact position indication
Yes
Device application
Nuclear
width (w)
36 mm
Colour
Grey
Local signalling
ON/OFF indication
Mounting mode
Clip-on
Net weight
284 g
wire stripping length
14 mm for top or bottom connection
Earth-leakage protection
Without
Mounting support
35 mm symmetrical DIN rail
depth
73 mm
mechanical durability
20000 cycles
electrical durability
3000 cycles L/R = 2 ms
6000 cycles
magnetic trip limit
8.3 x In +/- 20 %
Network type
DC
Pollution degree
3 conforming to EN/IEC 60947-2
Suitability for isolation
Yes
Poles description
2P
Utilisation category
Category A conforming to EN/IEC 60947-2
Environment
Ambient air temp for storage/transportation
-40…85 °C
ip degree of protection
IP20 conforming to IEC 60529
ambient air temperature for operation
-25…70 °C
overvoltage category
IV
standards
EN/IEC 60947-2
Tropicalisation
2 conforming to IEC 60068-2
relative humidity
95 % at 55 °C