Main
Device short name
GFP
Range
Multi9
Earth-leakage protection class
Type A-SI (Super Immunised)
Neutral position
Left
Earth-leakage protection time delay
Instantaneous
Earth-leakage sensitivity
86 mA conforming to UL 1053
100 mA conforming to EN/IEC 61008-1
Product Name
Multi9 GFP
[ui] rated insulation voltage
440 V AC 50/60 Hz
Complementary
9 mm pitches
8
[in] rated current
63 A at 40 °C conforming to EN/IEC 61008-1
[ue] rated operational voltage
415 V AC 50 Hz
480Y/277 V AC 60 Hz
[ics] rated service breaking capacity
Idm 1500 A conforming to EN/IEC 61008-1
Control type
Toggle
Product certifications
IEC
UL
Handle front plate colour
81 mm
Product or component type
Residual current circuit breaker (RCCB)
tightening torque
3.5 N.m top or bottom
[uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 61008-1
Connections - terminals
Tunnel type terminals (top or bottom) 1…25 mm² (AWG 18...AWG 3) - flexible
Tunnel type terminals (top or bottom) 1…35 mm² (AWG 18...AWG 2) - rigid
Tunnel type terminals (top or bottom) 1…25 mm² (AWG 18...AWG 3) - flexible with ferrule
Locking options description
Padlocking in OFF position
Contact position indication
Yes
Device application
Distribution
width (w)
72 mm
network frequency
50/60 Hz
Colour
Grey
Local signalling
ON, OFF, fault trip
Mounting mode
Clip-on
Net weight
0.45 kg
wire stripping length
14 mm for top or bottom connection
Mounting support
DIN rail
depth
60 mm
mechanical durability
20000 cycles
Network type
AC
Pollution degree
3
residual current tripping technology
Voltage independent
Rated conditional short-circuit current
Inc 10 kA 100 A gG
Poles description
4P
Utilisation category
AC-23A conforming to EN/IEC 61008-1
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP20 conforming to IEC 60529
IP40 (modular enclosure) conforming to IEC 60529
ambient air temperature for operation
-25…60 °C
electromagnetic compatibility
8/20 µs impulse withstand, 3000 A conforming to EN/IEC 61008-1
standards
EN/IEC 61008-1
UL 1053
Tropicalisation
2 conforming to IEC 60068-1
relative humidity
95 % at 55 °C