Main
Device short name
ID
Range
Multi9
Earth-leakage protection class
Type AC
Neutral position
Left
Earth-leakage protection time delay
Instantaneous
Earth-leakage sensitivity
30 mA
Product Name
Multi9 ID
[ui] rated insulation voltage
440 V AC 50 Hz conforming to EN/IEC 61008-1
Complementary
9 mm pitches
8
[in] rated current
40 A
[ue] rated operational voltage
380...415 V AC 50 Hz
[ics] rated service breaking capacity
Idm 400 A conforming to EN/IEC 61008-1
Control type
Toggle
Product certifications
CE
Handle front plate colour
81 mm
Product or component type
Residual current circuit breaker (RCCB)
tightening torque
3.5 N.m top or bottom
[uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 61008-1
Connections - terminals
Tunnel type terminal (top or bottom) 1…35 mm² - rigid
Tunnel type terminal (top or bottom) 1…25 mm² - flexible
Tunnel type terminal (top or bottom) 3 cable(s) 16 mm² - rigid
Tunnel type terminal (top or bottom) 3 cable(s) 10 mm² - flexible
Tunnel type terminal (top or bottom) 1…25 mm² - flexible with ferrule
Locking options description
Padlocking device
Contact position indication
Yes
Device application
Distribution
width (w)
72 mm
network frequency
50 Hz
Colour
Grey
Local signalling
ON, OFF, fault trip
Mounting mode
Clip-on
Net weight
0.45 kg
wire stripping length
15 mm for top or bottom connection
Mounting support
DIN rail
depth
73 mm
mechanical durability
20000 cycles
electrical durability
2000 cycles
Network type
AC
Pollution degree
3
residual current tripping technology
Voltage independent
Surge current
250 A
Rated conditional short-circuit current
Inc 10 kA
Poles description
4P
Environment
Ambient air temp for storage/transportation
-40…60 °C
ip degree of protection
IP20 conforming to IEC 60529
IP40 (modular enclosure) conforming to IEC 60529
ambient air temperature for operation
-5…40 °C
electromagnetic compatibility
8/20 µs impulse withstand, 250 A conforming to EN/IEC 61008-1
standards
EN/IEC 61008-1
Tropicalisation
2 conforming to IEC 60068-1
relative humidity
95 % at 55 °C