Additional Information
curve
C
Main
Device short name
C60SP
Range
Multi9
Number of protected poles
1
Product Name
Multi9 C60
Trip unit technology
Thermal-magnetic
[ui] rated insulation voltage
500 V AC conforming to EN/IEC 60947-2
Complementary
9 mm pitches
2
[in] rated current
1 A at 25 °C conforming to EN/IEC 60947-2
[ue] rated operational voltage
240 V AC 50/60 Hz
415 V AC 50/60 Hz
60 V DC
[ics] rated service breaking capacity
2.25 kA 75 % conforming to EN/IEC 60947-2 - 415 V AC
7.5 kA 75 % conforming to EN/IEC 60947-2 - 240 V AC
20 kA 100 % conforming to EN/IEC 60947-2 - 60 V DC
2.25 kA 75 % conforming to GB 14048.2 - 415 V AC
7.5 kA 75 % conforming to GB 14048.2 - 240 V AC
20 kA 100 % conforming to GB 14048.2 - 60 V DC
Control type
Toggle
Product certifications
IEC
CCC
UR
CSA
Handle front plate colour
81 mm
Product or component type
Miniature circuit-breaker
tightening torque
2.5 N.m top or bottom
[uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-2
Connections - terminals
Tunnel type terminal (top or bottom)1…25 mm² (AWG 18...AWG 8) - rigid
Tunnel type terminal (top or bottom)1…16 mm² (AWG 18...AWG 8) - flexible with ferrule
Tunnel type terminal (top or bottom)1…16 mm² (AWG 18...AWG 8) - flexible
Contact position indication
Yes
Device application
Distribution
width (w)
18 mm
Colour
Grey
Local signalling
ON/OFF indication
Mounting mode
Clip-on
wire stripping length
14 mm for top or bottom connection
Earth-leakage protection
Without
Mounting support
DIN rail
depth
72 mm
mechanical durability
20000 cycles
electrical durability
10000 cycles
magnetic trip limit
8.5 x In +/- 20 % AC
12 x In +/- 20 % DC
Network type
AC
DC
Pollution degree
3 conforming to EN/IEC 60947-2
Provision for padlocking
Padlockable
Suitability for isolation
Yes conforming to EN/IEC 60947-2
Poles description
1P
Environment
Ambient air temp for storage/transportation
-40…80 °C
ip degree of protection
IP20 conforming to IEC 60529
IP40 (modular enclosure) conforming to IEC 60529
operating altitude
0...2000 m
ambient air temperature for operation
-30…70 °C
standards
EN/IEC 60947-2
GB 14048.2
UL 1077
CSA C22.2 No 235
Tropicalisation
2 conforming to IEC 60068-1
relative humidity
95 % at 55 °C