Main
Device short name
LX4D8
Inductance of closed circuit
3.03 H
Range
TeSys
[uc] control circuit voltage
24 V DC
control circuit type
DC standard
Complementary
product compatibility
LC1D150
LC1D115
Average resistance
147 Ohm at 20 °C
Product or component type
Contactor coil
Control circuit voltage limits
Operational: 0.75...1.2 Uc (at <55 °C)
Drop-out: 0.15...0.4 Uc (at <55 °C)
Net weight
0.3 kg
time constant
25 ms
Hold-in power consumption in w
2.4…5.1 W at 20 °C
inrush power in w
270…365 W (at 20 °C)
mechanical durability
8 Mcycles
Maximum operating rate
1200 cyc/h 60 °C
coil technology
Without built-in suppressor module
Environment
ambient air temperature for operation
-5…60 °C