Main
Device short name
LX1FG
Inductance of closed circuit
0.65 H
Range
TeSys
[uc] control circuit voltage
110...115 V AC 50 Hz
control circuit type
AC at 50 Hz
Complementary
product compatibility
LC1F185
LC1F225
range compatibility
TeSys (TeSys F) LC1F contactor
Average resistance
4.18 Ohm at 20 °C
Product or component type
Contactor coil
Control circuit voltage limits
Drop-out: 0.35...0.55 Uc 50/60 Hz (at 55 °C)
Operational: 0.85...1.1 Uc 50/60 Hz (at 55 °C)
Heat dissipation
18…24 W at 50 Hz
Net weight
0.55 kg
Hold-in power consumption in va
55 VA 50 Hz cos phi 0.3 (at 20 °C)
Inrush power in va
805 VA 50 Hz cos phi 0.3 (at 20 °C)
mechanical durability
10 Mcycles
Maximum operating rate
2400 cyc/h 55 °C
operating time
20...35 ms closing
7...15 ms opening
coil technology
Without built-in suppressor module
Environment
ambient air temperature for operation
-5…55 °C