Main
Device short name
LX1D6
Inductance of closed circuit
22 H
Range
TeSys
[uc] control circuit voltage
380 V AC 50 Hz
control circuit type
AC at 50 Hz
Complementary
product compatibility
LC1D95
LC1D80
Average resistance
381 Ohm at 20 °C
Product or component type
Contactor coil
Control circuit voltage limits
Drop-out: 0.3...0.6 Uc at 50/60 Hz (at <55 °C)
Operational: 0.8...1.1 Uc at 50 Hz (at <55 °C)
Operational: 0.85...1.1 Uc at 60 Hz (at <55 °C)
Heat dissipation
6…10 W at 50/60 Hz
Net weight
0.28 kg
Hold-in power consumption in va
20 VA 50 Hz cos phi 0.3 (at 20 °C)
Inrush power in va
200 VA 50 Hz cos phi 0.75 (at 20 °C)
mechanical durability
10 Mcycles
Maximum operating rate
3600 cyc/h 60 °C
coil technology
Without built-in suppressor module
Environment
ambient air temperature for operation
-5…60 °C