Main
product range
Linergy
Range
Linergy
[ipk] rated peak withstand current
30 kA
busbar description
Barre isolée
type of product or equipment
Jeu de barres
i²t at switch-on
100000 kA².s
Product Name
Linergy BW
description d'installation
Cellule - largeur 650 mm
Armoire - largeur 600 mm
Coffret - largeur 600 mm
[ui] rated insulation voltage
750 V CA
Complementary
[ie] rated operational current
160 A
range compatibility
PrismaSeT (PrismaSeT G) boîtier
PrismaSeT (PrismaSeT P) boîtier
[icw] rated short-time withstand current
10 kA (1s)
length [l]
1400 mm
allowable current
160 A
batch quantity
Lot de 1
Handle front plate colour
85 mm
[uimp] rated impulse withstand voltage
8 kV
product weight
5,66 kg
facility management
Vertical, position de fonctionnement : arrière
mechanical robustness
Essais sismiques renforcement de structure - 2,5G se conformer à CEI 60068-2-57
no connection
Raccordement tous les 25 mm
type of connection with the busbar
Trou fileté
depth
45 mm
Poles description
4P
Environment
degree of protection (ip)
IPxx B
product certificates
ASTA
standards
CEI 61439-1
CEI 61439-2