Main
Device short name
CVS630N
Range
EasyPact
Earth leakage protection (vigi add on)
Without
Protected poles description
3D
Product Name
EasyPact CVS
Trip unit name
MA
Trip unit technology
Magnetic
Trip unit rating
500 A at 40 °C
Complementary
[in] rated current
500 A at 40 °C
compatibility code
CVS630
[ics] rated service breaking capacity
70 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
32 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
Control type
Toggle
Product certifications
IEC
GOST
[isd] short-time pick-up adjustment range
6...13 x In
Connection pitch
45 mm
Handle front plate colour
255 mm
Product or component type
Circuit breaker
[uimp] rated impulse withstand voltage
8 kV conforming to EN/IEC 60947-2
Connections - terminals
Screw connection
Breaking capacity code
N
Contact position indication
Yes
Device application
Motor
Electrical shock protection class
Class II
width (w)
140 mm
network frequency
50/60 Hz
Mounting mode
Fixed
Net weight
5.2 kg
Downside connection
Front
Mounting support
Backplate
depth
110 mm
mechanical durability
15000 cycles
electrical durability
4000 cycles 415 V In conforming to IEC 60947-2
Network type
AC
Pollution degree
3 conforming to IEC 60664-1
Instantaneous pick-up adjustment range
6...13 x In
Instantaneous pick-up adjustment type ii
Adjustable
Poles description
3P
Upside connection
Front
Utilisation category
Category A
Short-time pick-up adjustment type isd
Adjustable
Protection type
Short-circuit protection (magnetic)
Environment
Ambient air temp for storage/transportation
-50…85 °C
ip degree of protection
IP40
ambient air temperature for operation
-25…70 °C
standards
EN 60947-2
IEC 60947-2