Main
Device short name
CVS250B
Range
EasyPact
Earth leakage protection (vigi add on)
Without
Protected poles description
3D
Product Name
EasyPact CVS
Trip unit name
TM-D
Trip unit technology
Thermal-magnetic
Trip unit rating
250 A at 40 °C
thermal protection adjustment range
175…250 A
Complementary
[in] rated current
250 A at 40 °C
compatibility code
CVS250
[ics] rated service breaking capacity
15 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Control type
Toggle
Product certifications
IEC
GOST
Connection pitch
35 mm
Handle front plate colour
161 mm
Product or component type
Circuit breaker
[uimp] rated impulse withstand voltage
8 kV conforming to EN/IEC 60947-2
Connections - terminals
Screw connection
Breaking capacity code
B
Contact position indication
Yes
Device application
Distribution
Electrical shock protection class
Class II
width (w)
105 mm
network frequency
50/60 Hz
Mounting mode
Fixed
Net weight
2 kg
Downside connection
Front
Mounting support
Backplate
depth
86 mm
mechanical durability
20000 cycles
electrical durability
10000 cycles 415 V In conforming to IEC 60947-2
Network type
AC
Pollution degree
3 conforming to IEC 60664-1
Instantaneous pick-up adjustment range
2500 A
Instantaneous pick-up adjustment type ii
Fixed
Long time delay adjustment type
Fixed
Long time pick-up adjustment range
0.7...1 x In
Long time pick-up adjustment type ir
Adjustable
Poles description
3P
Upside connection
Front
Utilisation category
Category A
Protection type
Short-circuit protection (magnetic)
Overload protection (thermal)
Environment
Ambient air temp for storage/transportation
-50…85 °C
ip degree of protection
IP40
ambient air temperature for operation
-25…70 °C
standards
IEC 60947-2
EN 60947-2