Main
Range
ComPact
Protected poles description
3t
Trip unit name
TM-D
Trip unit technology
Thermal-magnetic
Trip unit rated current
200 A at 40 °C
Trip unit protection functions
LI
Complementary
[ue] rated operational voltage
750 V DC
range compatibility
ComPact NSX250 DC
Product certifications
ASEFA
KEMA
ASTA
LCIE
[ir] long-time protection pick-up adjustment range
0.7...1 x In
Product or component type
Trip unit
[isd] short-time protection pick-up adjustment range
5...10 x In
Device application
Distribution
long-time pick-up adjustment type ir (thermal protection)
Adjustable
long-time protection delay adjustment type tr
Fixed
Earth-leakage protection
Without
Network type
DC
short-time protection delay adjustment type tsd
Fixed
short-time protection pick-up adjustment type isd
Adjustable
Poles description
3P
Protection type
L : for overload protection (thermal)
I : for short-circuit protection (magnetic)
Environment
Ambient air temp for storage/transportation
-50…85 °C
Range of product
ComPact NSX100...250 DC
ambient air temperature for operation
-25…70 °C
standards
IEC 60947-2