Main
Device short name
VigiPacT
[δt] residual earth-leakage time delay adjustment
0 ms
60 ms
150 ms
300 ms
500 ms
800 ms
1.2 s
4 s
Earth-leakage protection class
Class A
Class AC
Earth-leakage sensitivity
0.03 A for class A
0.1 A for class A
0.3 A for class A
0.5 A for class A
1 A for class A
3 A for class A
10 A for class AC
30 A for class AC
Residual earth-leakage time delay adjustment type
Adjustable
Residual earth-leakage sensitity adjustment type
Adjustable
Complementary
[in] rated current
250 A
[ue] rated operational voltage
440...550 V AC 50/60 Hz conforming to IEC 60947-2
range compatibility
ComPacT new generation (ComPacT NSX250 new generation) circuit breaker
ComPact (ComPact NSX250) circuit breaker
Product or component type
Vigi add-on
Maximum breaking time
800 ms
Device application
Wiring
Electrical shock protection class
Class II
network frequency
50/60 Hz
Earth-leakage protection
With
Network type
AC
Poles description
3P
Environment
Range of product
ComPacT NSX100...250 new generation
ComPact NSX100...250
overvoltage category
IV
standards
IEC 60947-2