All categories
Compare Cart

LV426372 - circuit breaker ComPact NSXm F (36 kA at 415 VAC), 4P 4d, 32 A rating TMD trip unit, compression lugs and busbar connectors - Schneider Electric

Expected in 2-4 weeks
LV426372 - circuit breaker ComPact NSXm F (36 kA at 415 VAC), 4P 4d, 32 A rating TMD trip unit, compression lugs and busbar connectors - Schneider Electric - circuit breaker ComPact NSXm F (36 kA at 415 VAC), 4P 4d, 32 A rating TMD trip unit, compression lugs and busbar connectors - Schneider Electric - 0
LV426372 - circuit breaker ComPact NSXm F (36 kA at 415 VAC), 4P 4d, 32 A rating TMD trip unit, compression lugs and busbar connectors - Schneider Electric
261,51 € excl. VAT
319,05 € incl. VAT
Text About:
circuit breaker ComPact NSXm F (36 kA at 415 VAC), 4P 4d, 32 A rating TMD trip unit, compression lugs and busbar connectors - Schneider Electric
319,05 €
SPECIFICATIONS
Main
Device short name NSXm 32F
Range ComPact
circuit breaker mounting mode By screws
Clip-on
Neutral position Left
Protected poles description 4D
Product Name ComPact NSXm
Trip unit name TM-D
Trip unit technology Thermal-magnetic
Trip unit rating 32 A at 40 °C
[ui] rated insulation voltage 800 V AC 50/60 Hz
Trip unit protection functions LI
performance level F 36 kA 415 V AC
Complementary
9 mm pitches 12 module
[in] rated current 32 A at 40 °C
[ue] rated operational voltage 690 V AC 50/60 Hz
[ics] rated service breaking capacity 10 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
85 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
36 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
[im] magnetic protection pick-up range 600 A
Control type Toggle
depth (d) 80 mm
Product certifications CCC
EAC
Marine
[ir] long-time protection pick-up adjustment range 0.7...1 x In
Connection pitch 35 mm with spreaders
27 mm without spreaders
Handle front plate colour 137 mm
Product or component type Circuit breaker
[uimp] rated impulse withstand voltage 8 kV
connection terminals compression lug/busbar
Device application Distribution
Protection
width (w) 108 mm
network frequency 50/60 Hz
Colour Grey (RAL 7016)
Ik degree of protection IK07 conforming to IEC 62262
long-time pick-up adjustment type ir (thermal protection) Adjustable
Net weight 1.42 kg
long-time protection delay adjustment type tr Fixed
number of slots for electrical auxiliaries 1 slot(s) for auxiliary switch OF
1 slot(s) for alarm switch SD
1 slot(s) for voltage release MN or MX
Earth-leakage protection Without
Mounting support Plate
DIN rail
mechanical durability 20000 cycles
electrical durability 10000 cycles at 440 V In
20000 cycles at 440 V In/2
5000 cycles at 690 V In
10000 cycles at 690 V In/2
Network type AC
Pollution degree 3 conforming to IEC 60664-1
Suitability for isolation Yes conforming to EN/IEC 60947-2
Poles description 4P
Utilisation category Category A
Protection type L : for overload protection (thermal)
I : for short-circuit protection (magnetic)
Environment
Ambient air temp for storage/transportation -50…85 °C
ip degree of protection IP40 conforming to IEC 60529
operating altitude 0...2000 m without derating
2000...5000 m with derating
Range of product ComPact NSXm
ambient air temperature for operation -25…70 °C
standards EN/IEC 60947
relative humidity 0…95 %
Recently viewed
261,51 € excl. VAT
319,05 € incl. VAT
Expected in 2-4 weeks