Main
																					
												Device short name
												LUCM
											
                            
																					
												product specific application
												Most sophisticated control and protection requirements, with display
											
                            
																					
												Range
												TeSys
											
                            
																					
												[uc] control circuit voltage
												24 V DC
											
                            
																					
												thermal overload class
												Class 5…30 - frequency limit: 50…60 Hz - temperature compensation: -25…55 °C conforming to IEC 60947-6-2
Class 5…30 - frequency limit: 50…60 Hz - temperature compensation: -25…55 °C conforming to UL 508
											
                            
																					
												user language
												English - setting factory setting
English, French, German, Italian, Spanish - setting settable
											
                            
																					
												Product Name
												TeSys Ultra
											
                            
																					
												Rated motor current adjustment range
												0.35…1.4 A
											
                            
																					
												[ui] rated insulation voltage
												690 V conforming to IEC 60947-6-2
600 V conforming to UL 60947-4-1
600 V conforming to CSA C22.2 No 60947-4-1
											
                            
																					
												main function available
												Protection against phase failure and phase imbalance
Protection function alarm
Protection against overload and short-circuit
Log function
Earth fault protection
Monitoring function, indication of main motor parameters
Differentiation of thermal overload and magnetic fault
Overload, no-load running
Manual or automatic reset
											
                            
																					
												reset
												Automatic reset - setting: setting range
Manual - setting: factory setting
Manual - setting: setting range
Remote reset - setting: setting range
											
                            
																					
												motor power kW
												0.25 kW at 400...440 V AC 50/60 Hz for 3 phases motors
0.09 kW at 400...440 V AC 50/60 Hz for 1 phase motors
											
                            
																			 
																	
										Complementary
																					
												product compatibility
												Power base LUB12
Power base LUB32
Power base LUB38
Power base LUB120
Power base LUB320
Power base LUB380
Reversing contactor breaker LU2B12BL
Reversing contactor breaker LU2B32BL
Reversing contactor breaker LU2B38BL
											
                            
																					
												[ue] rated operational voltage
												690 V AC
											
                            
																					
												compatibility code
												LUCM
											
                            
																					
												Product certifications
												CE
UL
CSA
CCC
EAC
ASEFA
ATEX
Marine
											
                            
																					
												Handle front plate colour
												66 mm
											
                            
																					
												Product or component type
												Multifunction control unit
											
                            
																					
												[uimp] rated impulse withstand voltage
												6 kV conforming to IEC 60947-6-2
											
                            
																					
												Device application
												Motor control
Motor protection
											
                            
																					
												Fixing mode
												Plug-in (front face)
											
                            
																					
												Control circuit voltage limits
												20...28 V for DC circuit 24 V in operation
14.5 V for DC circuit 24 V drop-out
											
                            
																					
												information displayed
												Average current (factory setting)
Average current (settable)
Cause of last 5 faults (settable)
Current in phase (settable)
Earth leakage current (settable)
Phase imbalance (settable)
Thermal state of motor (settable)
											
                            
																					
												width (w)
												45 mm
											
                            
																					
												network frequency
												40...60 Hz
											
                            
																					
												Heat dissipation
												1.7 W for control circuit with LUB12
1.8 W for control circuit with LUB32
1.8 W for control circuit with LUB38
0.8 W for external auxiliary circuit
											
                            
																					
												Net weight
												0.175 kg
											
                            
																					
												physical interface
												RS485 multidrop - connector(s): RJ45 - location: front panel - communication protocol: Modbus RTU 19200 bit/s
											
                            
																					
												Immunity to microbreaks
												3 ms
											
                            
																					
												depth
												60 mm
											
                            
																					
												Load type
												3-phase motor - cooling: self-cooled - setting factory setting
3-phase motor - cooling: self-cooled, force cooled - setting settable
Single-phase motor - cooling: self-cooled, force cooled - setting settable
											
                            
																					
												Messages display capacity
												2 lines of 12 characters - display LCD - English - accuracy +/- 5 % - resolution 1 % of Ir
2 lines of 12 characters - display LCD - French - accuracy +/- 5 % - resolution 1 % of Ir
2 lines of 12 characters - display LCD - German - accuracy +/- 5 % - resolution 1 % of Ir
2 lines of 12 characters - display LCD - Italian - accuracy +/- 5 % - resolution 1 % of Ir
2 lines of 12 characters - display LCD - Spanish - accuracy +/- 5 % - resolution 1 % of Ir
											
                            
																					
												operating time
												35 ms opening with LUB12 for control circuit
35 ms opening with LUB32 for control circuit
35 ms opening with LUB38 for control circuit
75 ms closing with LUB12 for control circuit
65 ms closing with LUB32 for control circuit
65 ms closing with LUB38 for control circuit
											
                            
																					
												Immunity to radioelectric fields
												10 V conforming to IEC 61000-4-6
											
                            
																					
												Tripping threshold
												14.2 x Ir +/- 20 %
											
                            
																					
												Resistance to electrostatic discharge
												8 kV level 3 in open air conforming to IEC 61000-4-2
8 kV level 4 on contact conforming to IEC 61000-4-2
											
                            
																					
												Shock resistance
												10 gn power poles open conforming to IEC 60068-2-27
15 gn power poles closed conforming to IEC 60068-2-27
											
                            
																					
												Return time
												<= 200 ms
											
                            
																					
												Safe separation of circuit
												400 V SELV between the control and auxiliary circuits conforming to IEC 60947-1
400 V SELV between the control or auxiliary circuit and the main circuit conforming to IEC 60947-1
											
                            
																					
												Time before reset
												1…1000 s - reset manual or automatic reset - setting settable
120 s - reset manual - setting factory setting
											
                            
																					
												Utilisation category
												AC-43
AC-44
AC-41
											
                            
																					
												Typical current consumption
												150 mA at 24 V DC I maximum while closing with LUB12
200 mA at 24 V DC I maximum while closing with LUB32
200 mA at 24 V DC I maximum while closing with LUB38
70 mA at 24 V DC I rms sealed with LUB12
75 mA at 24 V DC I rms sealed with LUB32
75 mA at 24 V DC I rms sealed with LUB38
											
                            
																			 
																	
										Environment
																					
												Ambient air temp for storage/transportation
												-40…85 °C
											
                            
																					
												ip degree of protection
												IP20 front panel and wired terminals conforming to IEC 60947-1
IP20 other faces conforming to IEC 60947-1
IP40 front panel outside connection zone conforming to IEC 60947-1
											
                            
																					
												operating altitude
												2000 m
											
                            
																					
												Range of product
												TeSys Ultra
											
                            
																					
												ambient air temperature for operation
												-25…60 °C
											
                            
																					
												Non-dissipating shock wave
												1 kV serial mode conforming to IEC 60947-6-2
2 kV common mode conforming to IEC 60947-6-2
											
                            
																					
												standards
												EN 60947-6-2
IEC 60947-6-2
UL 60947-4-1, with phase barrier
CSA C22.2 No 60947-4-1, with phase barrier
											
                            
																					
												fire resistance
												960 °C parts supporting live components conforming to IEC 60695-2-12
650 °C conforming to IEC 60695-2-12
											
                            
																					
												immunity to voltage dips
												70 % / 500 ms conforming to IEC 61000-4-11
											
                            
																					
												resistance to radiated fields
												10 V/m 3 conforming to IEC 61000-4-3
											
                            
																					
												vibration resistance
												2 gn, 5…300 Hz, power poles open conforming to IEC 60068-2-6
4 gn, 5…300 Hz, power poles closed conforming to IEC 60068-2-6
											
                            
																					
												protective treatment
												TH conforming to IEC 60068
											
                            
																					
												resistance to fast transients
												2 kV class 3 serial link conforming to IEC 61000-4-4
4 kV class 4 all circuits except for serial link conforming to IEC 61000-4-4