Main
Device short name
LUCL
product specific application
Protection of variable speed drive or soft startsoft stop unit
Range
TeSys
[uc] control circuit voltage
48 V AC
48...72 V DC
Product Name
TeSys Ultra
Rated motor current adjustment range
3…12 A
[ui] rated insulation voltage
690 V conforming to IEC 60947-6-2
600 V conforming to UL 60947-4-1
600 V conforming to CSA C22.2 No 60947-4-1
main function available
Short-circuit protection
Manual reset
motor power kW
5.5 kW at 400...440 V AC 50/60 Hz
5.5 kW at 500 V AC 50/60 Hz
9 kW at 690 V AC 50/60 Hz
Complementary
product compatibility
Power base LUB12
Power base LUB32
Power base LUB38
Power base LUB120
Power base LUB320
Power base LUB380
Reversing contactor breaker LU2B12ES
Reversing contactor breaker LU2B32ES
[ue] rated operational voltage
690 V AC
compatibility code
LUCL
Product certifications
CE
UL
CSA
CCC
EAC
ASEFA
ATEX
Marine
Handle front plate colour
66 mm
Product or component type
Magnetic control unit
[uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947-6-2
Device application
Motor control
Motor protection
Fixing mode
Plug-in (front face)
Control circuit voltage limits
38.5...72 V for AC circuit 48 V in operation
38.5...93 V for DC circuit 48...72 V in operation
29 V for AC circuit 48 V drop-out
29 V for DC circuit 48...72 V drop-out
width (w)
45 mm
network frequency
40...60 Hz
Heat dissipation
2 W for control circuit with LUB12
3 W for control circuit with LUB32
3 W for control circuit with LUB38
Net weight
0.135 kg
Immunity to microbreaks
3 ms
depth
60 mm
Load type
3-phase motor - cooling: self-cooled
operating time
35 ms opening with LUB12 for control circuit
35 ms opening with LUB32 for control circuit
35 ms opening with LUB38 for control circuit
60 ms closing with LUB12 for control circuit
60 ms closing with LUB32 for control circuit
60 ms closing with LUB38 for control circuit
Immunity to radioelectric fields
10 V conforming to IEC 61000-4-6
Tripping threshold
14.2 x Ir +/- 20 %
Resistance to electrostatic discharge
8 kV level 3 in open air conforming to IEC 61000-4-2
8 kV level 4 on contact conforming to IEC 61000-4-2
Shock resistance
10 gn power poles open conforming to IEC 60068-2-27
15 gn power poles closed conforming to IEC 60068-2-27
Safe separation of circuit
400 V SELV between the control and auxiliary circuits conforming to IEC 60947-1
400 V SELV between the control or auxiliary circuit and the main circuit conforming to IEC 60947-1
Utilisation category
AC-41
AC-43
AC-44
Typical current consumption
280 mA at 48 V AC I maximum while closing with LUB12
280 mA at 48 V AC I maximum while closing with LUB32
280 mA at 48 V AC I maximum while closing with LUB38
280 mA at 48...72 V DC I maximum while closing with LUB12
280 mA at 48...72 V DC I maximum while closing with LUB32
280 mA at 48...72 V DC I maximum while closing with LUB38
35 mA at 48 V AC I rms sealed with LUB12
45 mA at 48 V AC I rms sealed with LUB32
45 mA at 48 V AC I rms sealed with LUB38
35 mA at 48...72 V DC I rms sealed with LUB12
45 mA at 48...72 V DC I rms sealed with LUB32
45 mA at 48...72 V DC I rms sealed with LUB38
Environment
Ambient air temp for storage/transportation
-40…85 °C
ip degree of protection
IP20 front panel and wired terminals conforming to IEC 60947-1
IP20 other faces conforming to IEC 60947-1
IP40 front panel outside connection zone conforming to IEC 60947-1
operating altitude
2000 m
Range of product
TeSys Ultra
ambient air temperature for operation
-25…70 °C
Non-dissipating shock wave
1 kV serial mode conforming to IEC 60947-6-2
2 kV common mode conforming to IEC 60947-6-2
standards
EN 60947-6-2
IEC 60947-6-2
UL 60947-4-1, with phase barrier
CSA C22.2 No 60947-4-1, with phase barrier
fire resistance
960 °C parts supporting live components conforming to IEC 60695-2-12
650 °C conforming to IEC 60695-2-12
immunity to voltage dips
70 % / 500 ms conforming to IEC 61000-4-11
resistance to radiated fields
10 V/m 3 conforming to IEC 61000-4-3
vibration resistance
2 gn, 5…300 Hz, power poles open conforming to IEC 60068-2-6
4 gn, 5…300 Hz, power poles closed conforming to IEC 60068-2-6
protective treatment
TH conforming to IEC 60068
resistance to fast transients
2 kV class 3 serial link conforming to IEC 61000-4-4
4 kV class 4 all circuits except for serial link conforming to IEC 61000-4-4