All categories
Compare Cart

LUCD12FU - Advanced control unit, TeSys Ultra, 3P, 3 to 12A, 690VAC, protection & diagnostic, class 20, 110 to 240VAC/DC coil - Schneider Electric

Expected in 2-4 weeks
LUCD12FU - Advanced control unit, TeSys Ultra, 3P, 3 to 12A, 690VAC, protection & diagnostic, class 20, 110 to 240VAC/DC coil - Schneider Electric - Advanced control unit, TeSys Ultra, 3P, 3 to 12A, 690VAC, protection & diagnostic, class 20, 110 to 240VAC/DC coil - Schneider Electric - 0
LUCD12FU - Advanced control unit, TeSys Ultra, 3P, 3 to 12A, 690VAC, protection & diagnostic, class 20, 110 to 240VAC/DC coil - Schneider Electric
118,91 € excl. VAT
145,07 € incl. VAT
Text About:
Advanced control unit, TeSys Ultra, 3P, 3 to 12A, 690VAC, protection & diagnostic, class 20, 110 to 240VAC/DC coil - Schneider Electric
145,07 €
SPECIFICATIONS
Main
Device short name LUCD
product specific application Basic protection and advanced functions, communication
Range TeSys
[uc] control circuit voltage 110...240 V AC
110...220 V DC
thermal overload class Class 20 - frequency limit: 40…60 Hz - temperature compensation: -25…70 °C conforming to IEC 60947-6-2
Class 20 - frequency limit: 40…60 Hz - temperature compensation: -25…70 °C conforming to UL 508
Product Name TeSys Ultra
Rated motor current adjustment range 3…12 A
[ui] rated insulation voltage 690 V conforming to IEC 60947-6-2
600 V conforming to UL 60947-4-1
600 V conforming to CSA C22.2 No 60947-4-1
main function available Protection against phase failure and phase imbalance
Manual reset
Earth fault protection
Protection against overload and short-circuit
reset Manual reset
motor power kW 5.5 kW at 400...440 V AC 50/60 Hz
5.5 kW at 500 V AC 50/60 Hz
9 kW at 690 V AC 50/60 Hz
Complementary
product compatibility Power base LUB12
Power base LUB32
Power base LUB38
Power base LUB120
Power base LUB320
Power base LUB380
Reversing contactor breaker LU2B12FU
Reversing contactor breaker LU2B32FU
Reversing contactor breaker LU2B38FU
[ue] rated operational voltage 690 V AC
compatibility code LUCD
Product certifications CE
UL
CSA
CCC
EAC
ASEFA
ATEX
Marine
Handle front plate colour 66 mm
Product or component type Advanced control unit
[uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-6-2
Device application Motor control
Motor protection
Fixing mode Plug-in (front face)
Control circuit voltage limits 88...264 V for AC circuit 110...240 V in operation
88...242 V for DC circuit 110...220 V in operation
55 V for AC circuit 110...240 V drop-out
55 V for DC circuit 110...220 V drop-out
width (w) 45 mm
network frequency 40...60 Hz
Heat dissipation 2 W for control circuit with LUB12
3 W for control circuit with LUB32
3 W for control circuit with LUB38
Immunity to microbreaks 3 ms
depth 60 mm
Load type 3-phase motor - cooling: self-cooled
operating time 35 ms opening with LUB12 for control circuit
35 ms opening with LUB32 for control circuit
35 ms opening with LUB38 for control circuit
50 ms closing with LUB12 for control circuit
50 ms closing with LUB32 for control circuit
50 ms closing with LUB38 for control circuit
Immunity to radioelectric fields 10 V conforming to IEC 61000-4-6
Phase failure sensitivity Yes
Tripping threshold 14.2 x Ir +/- 20 %
Resistance to electrostatic discharge 8 kV level 3 in open air conforming to IEC 61000-4-2
8 kV level 4 on contact conforming to IEC 61000-4-2
Shock resistance 10 gn power poles open conforming to IEC 60068-2-27
15 gn power poles closed conforming to IEC 60068-2-27
Safe separation of circuit 400 V SELV between the control and auxiliary circuits conforming to IEC 60947-1
400 V SELV between the control or auxiliary circuit and the main circuit conforming to IEC 60947-1
Utilisation category AC-44
AC-41
AC-43
Typical current consumption 280 mA at 110...240 V AC I maximum while closing with LUB12
280 mA at 110...240 V AC I maximum while closing with LUB32
280 mA at 110...240 V AC I maximum while closing with LUB38
280 mA at 110...220 V DC I maximum while closing with LUB12
280 mA at 110...220 V DC I maximum while closing with LUB32
280 mA at 110...220 V DC I maximum while closing with LUB38
35 mA at 110...240 V AC I rms sealed with LUB12
25 mA at 110...240 V AC I rms sealed with LUB32
25 mA at 110...240 V AC I rms sealed with LUB38
35 mA at 110...220 V DC I rms sealed with LUB12
25 mA at 110...220 V DC I rms sealed with LUB32
25 mA at 110...220 V DC I rms sealed with LUB38
Environment
Ambient air temp for storage/transportation -40…85 °C
ip degree of protection IP20 front panel and wired terminals conforming to IEC 60947-1
IP20 other faces conforming to IEC 60947-1
IP40 front panel outside connection zone conforming to IEC 60947-1
operating altitude 2000 m
Range of product TeSys Ultra
ambient air temperature for operation -25…70 °C
Non-dissipating shock wave 1 kV serial mode conforming to IEC 60947-6-2
2 kV common mode conforming to IEC 60947-6-2
standards EN 60947-6-2
IEC 60947-6-2
UL 60947-4-1, with phase barrier
CSA C22.2 No 60947-4-1, with phase barrier
fire resistance 960 °C parts supporting live components conforming to IEC 60695-2-12
650 °C conforming to IEC 60695-2-12
immunity to voltage dips 70 % / 500 ms conforming to IEC 61000-4-11
resistance to radiated fields 10 V/m 3 conforming to IEC 61000-4-3
vibration resistance 2 gn, 5…300 Hz, power poles open conforming to IEC 60068-2-6
4 gn, 5…300 Hz, power poles closed conforming to IEC 60068-2-6
protective treatment TH conforming to IEC 60068
resistance to fast transients 2 kV class 3 serial link conforming to IEC 61000-4-4
4 kV class 4 all circuits except for serial link conforming to IEC 61000-4-4
Recently viewed
118,91 € excl. VAT
145,07 € incl. VAT
Expected in 2-4 weeks