Complementary
																					
												[ie] rated operational current
												35 A at <= 440 V
28 A at 500 V
24 A at 690 V
											
                            
																					
												[ue] rated operational voltage
												690 V AC for power circuit
											
                            
																					
												compatibility code
												LUB
											
                            
																					
												[ics] rated service breaking capacity
												25 kA at 230 V
25 kA at 440 V
10 kA at 500 V
4 kA at 690 V
											
                            
																					
												[ith] conventional thermal current
												38 A
											
                            
																					
												Product certifications
												CE
UL
CSA
CCC
EAC
											
                            
																					
												Handle front plate colour
												154 mm
											
                            
																					
												Product or component type
												Non reversing power base
											
                            
																					
												tightening torque
												Control circuit: 0.8…1.2 N.m flat screwdriver 5 mm
Control circuit: 0.8…1.2 N.m Philips no 1 screwdriver 5 mm
Power circuit: 1.9…2.5 N.m flat screwdriver 6 mm
Power circuit: 1.9…2.5 N.m Philips No 2 screwdriver 6 mm
Power circuit: 1.9…2.5 N.m pozidriv No 2 screwdriver 6 mm
											
                            
																					
												[uimp] rated impulse withstand voltage
												6 kV conforming to IEC 60947-6-2
											
                            
																					
												Auxiliary contact composition
												1 NO + 1 NC
											
                            
																					
												Connections - terminals
												Control circuit: screw clamp terminals 1 cable(s) 0.34…1.5 mm² flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 0.75…1.5 mm² flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 0.75…1.5 mm² rigid
Control circuit: screw clamp terminals 2 cable(s) 0.34…1.5 mm² flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 0.75…1.5 mm² flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 0.75…1.5 mm² rigid
Power circuit: screw clamp terminals 1 cable(s) 1…10 mm² rigid
Power circuit: screw clamp terminals 1 cable(s) 1…6 mm² flexible with cable end
Power circuit: screw clamp terminals 1 cable(s) 2.5…10 mm² flexible without cable end
Power circuit: screw clamp terminals 2 cable(s) 1…6 mm² flexible with cable end
Power circuit: screw clamp terminals 2 cable(s) 1…6 mm² rigid
Power circuit: screw clamp terminals 2 cable(s) 1.5…6 mm² flexible without cable end
											
                            
																					
												Auxiliary contacts type
												type linked contacts (1 NO + 1 NC) conforming to IEC 60947-4-1
 type mirror contact (1 NC) conforming to IEC 60947-1
											
                            
																					
												Device application
												Motor control
Motor protection
											
                            
																					
												Fixing mode
												Clipped (DIN rail)
Screw-fixed (plate)
											
                            
																					
												width (w)
												45 mm
											
                            
																					
												network frequency
												40...60 Hz
											
                            
																					
												Heat dissipation
												3 W for control circuit with LUCA, LUCB, LUCC, LUCD
1.8 W for control circuit with LUCM
											
                            
																					
												Net weight
												0.9 kg
											
                            
																					
												Immunity to microbreaks
												3 ms for control circuit
											
                            
																					
												depth
												126 mm
											
                            
																					
												mechanical durability
												15 Mcycles
											
                            
																					
												Maximum operating rate
												3600 cyc/h
											
                            
																					
												operating time
												35 ms opening with LUCA, LUCB, LUCC, LUCD, LUCM for control circuit
50 ms at >= 72 V closing with LUCA, LUCB, LUCC, LUCD for control circuit
60 ms at 48 V closing with LUCA, LUCB, LUCC, LUCD for control circuit
70 ms at 24 V closing with LUCA, LUCB, LUCC, LUCD for control circuit
65 ms closing with LUCM for control circuit
											
                            
																					
												Immunity to radioelectric fields
												10 V conforming to IEC 61000-4-6
											
                            
																					
												Resistance to electrostatic discharge
												8 kV level 3 in open air conforming to IEC 61000-4-2
8 kV level 4 on contact conforming to IEC 61000-4-2
											
                            
																					
												Shock resistance
												10 gn power poles open conforming to IEC 60068-2-27
15 gn power poles closed conforming to IEC 60068-2-27
											
                            
																					
												Suitability for isolation
												Yes
											
                            
																					
												Poles description
												3P
											
                            
																					
												Safe separation of circuit
												400 V SELV between the control and auxiliary circuits conforming to IEC 60947-1 appendix N
400 V SELV between the control or auxiliary circuit and the main circuit conforming to IEC 60947-1 appendix N
											
                            
																					
												Utilisation category
												AC-43
AC-41
											
                            
																					
												Typical current consumption
												200 mA at 24 V DC I maximum while closing with LUCM
220 mA at 24 V AC I maximum while closing with LUCA, LUCB, LUCC, LUCD
220 mA at 24 V DC I maximum while closing with LUCA, LUCB, LUCC, LUCD
25 mA at 110...220 V DC I rms sealed with LUCA, LUCB, LUCC, LUCD
25 mA at 110...240 V AC I rms sealed with LUCA, LUCB, LUCC, LUCD
280 mA at 110...220 V DC I maximum while closing with LUCA, LUCB, LUCC, LUCD
280 mA at 110...240 V AC I maximum while closing with LUCA, LUCB, LUCC, LUCD
280 mA at 48...72 V AC I maximum while closing with LUCA, LUCB, LUCC, LUCD
280 mA at 48...72 V DC I maximum while closing with LUCA, LUCB, LUCC, LUCD
45 mA at 48...72 V AC I rms sealed with LUCA, LUCB, LUCC, LUCD
45 mA at 48...72 V DC I rms sealed with LUCA, LUCB, LUCC, LUCD
75 mA at 24 V DC I rms sealed with LUCM
80 mA at 24 V DC I rms sealed with LUCA, LUCB, LUCC, LUCD
90 mA at 24 V AC I rms sealed with LUCA, LUCB, LUCC, LUCD
											
                            
																					
												Safety reliability level
												B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
											
                            
																			 
																	
										Environment
																					
												Ambient air temp for storage/transportation
												-40…85 °C
											
                            
																					
												ip degree of protection
												IP20 conforming to IEC 60947-1 (front panel and wired terminals)
IP20 conforming to IEC 60947-1 (other faces)
IP40 conforming to IEC 60947-1 (front panel outside connection zone)
											
                            
																					
												operating altitude
												2000 m
											
                            
																					
												ambient air temperature for operation
												-25…60 °C with LUCM
-25…70 °C with LUCA, LUCB, LUCC, LUCD
											
                            
																					
												Non-dissipating shock wave
												1 kV serial mode 24...240 V AC conforming to IEC 60947-6-2
1 kV serial mode 48...220 V DC conforming to IEC 60947-6-2
2 kV common mode 24...240 V AC conforming to IEC 60947-6-2
2 kV common mode 48...220 V DC conforming to IEC 60947-6-2
											
                            
																					
												standards
												EN 60947-6-2
IEC 60947-6-2
UL 60947-4-1, with phase barrier
CSA C22.2 No 60947-4-1, with phase barrier
											
                            
																					
												fire resistance
												960 °C parts supporting live components conforming to IEC 60695-2-12
650 °C conforming to IEC 60695-2-12
											
                            
																					
												immunity to voltage dips
												70 % / 500 ms conforming to IEC 61000-4-11
											
                            
																					
												resistance to radiated fields
												10 V/m 3 conforming to IEC 61000-4-3
											
                            
																					
												vibration resistance
												2 gn (f= 5…300 Hz) power poles open conforming to IEC 60068-2-27
4 gn (f= 5…300 Hz) power poles closed conforming to IEC 60068-2-27
											
                            
																					
												protective treatment
												TH conforming to IEC 60068
											
                            
																					
												resistance to fast transients
												2 kV class 3 serial link conforming to IEC 61000-4-4
4 kV class 4 all circuits except for serial link conforming to IEC 61000-4-4