Main
Device short name
LU6MB
Range
TeSys
[uc] control circuit voltage
24 V DC
device mounting
Separate mounting
[ui] rated insulation voltage
690 V conforming to IEC 60947-6-2
600 V conforming to UL 60947-4-1
600 V conforming to CSA C22.2 No 60947-4-1
Complementary
[ie] rated operational current
38 A
[ue] rated operational voltage
690 V AC power circuit
compatibility code
LU6MB
Product certifications
CE
UL
CSA
CCC
EAC
ASEFA
ATEX
Marine
Handle front plate colour
115 mm
Product or component type
Reverser block
tightening torque
Control circuit: 0.8…1.2 N.m flat screwdriver 5 mm
Control circuit: 0.8…1.2 N.m Philips No 2 screwdriver 5 mm
Power circuit: 1.9…2.5 N.m flat screwdriver 6 mm
Power circuit: 1.9…2.5 N.m Philips No 2 screwdriver 6 mm
Power circuit: 1.9…2.5 N.m pozidriv No 2 screwdriver 6 mm
[uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947-6-2
Current consumption
120 mA at 24 V DC I maximum while closing
120 mA at 24 V DC I rms sealed
Connections - terminals
Control circuit: screw clamp terminals 1 cable(s) 0.34…1.5 mm² (external diameter: 3 mm) flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 0.75…1.5 mm² (external diameter: 3 mm) flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 0.75…1.5 mm² (external diameter: 3 mm) rigid
Control circuit: screw clamp terminals 2 cable(s) 0.34…1.5 mm² (external diameter: 3 mm) flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 0.75…1.5 mm² (external diameter: 3 mm) flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 0.75…1.5 mm² (external diameter: 3 mm) rigid
Power circuit: screw clamp terminals 1 cable(s) 1…10 mm² (external diameter: 4 mm) rigid
Power circuit: screw clamp terminals 1 cable(s) 1…6 mm² (external diameter: 4 mm) flexible with cable end
Power circuit: screw clamp terminals 1 cable(s) 2.5…10 mm² (external diameter: 4 mm) flexible without cable end
Power circuit: screw clamp terminals 2 cable(s) 1…6 mm² (external diameter: 4 mm) flexible with cable end
Power circuit: screw clamp terminals 2 cable(s) 1…6 mm² (external diameter: 4 mm) rigid
Power circuit: screw clamp terminals 2 cable(s) 1.5…6 mm² (external diameter: 4 mm) flexible without cable end
Device application
Motor control
Fixing mode
Clipped (DIN rail)
Screw-fixed (plate)
width (w)
45 mm
network frequency
40...60 Hz
Net weight
0.425 kg
depth
113 mm
operating time
150 ms with change of direction
75 ms without change of direction
Immunity to radioelectric fields
10 V conforming to IEC 61000-4-6
Inrush restraint duration
25 ms AC
15 ms DC
Resistance to electrostatic discharge
8 kV level 3, in open air conforming to IEC 61000-4-2
8 kV level 4, on contact conforming to IEC 61000-4-2
Shock resistance
10 gn power poles open conforming to IEC 60068-2-27
15 gn power poles closed conforming to IEC 60068-2-27
Environment
Ambient air temp for storage/transportation
-40…85 °C
ip degree of protection
IP20 conforming to IEC 60947-1 (front panel and wired terminals)
IP20 conforming to IEC 60947-1 (other faces)
IP40 conforming to IEC 60947-1 (front panel outside connection zone)
operating altitude
2000 m
ambient air temperature for operation
-25…60 °C with LUCM
-25…70 °C with LUCA, LUCB, LUCC, LUCD
standards
EN 60947-6-2
IEC 60947-6-2
UL 60947-4-1, with phase barrier
CSA C22.2 No 60947-4-1, with phase barrier
fire resistance
960 °C parts supporting live components conforming to IEC 60695-2-12
650 °C conforming to IEC 60695-2-12
resistance to radiated fields
10 V/m level 3 conforming to IEC 61000-4-3
vibration resistance
2 gn (f= 5…300 Hz) power poles open conforming to IEC 60068-2-27
4 gn (f= 5…300 Hz) power poles closed conforming to IEC 60068-2-27
protective treatment
TH conforming to IEC 60068
resistance to fast transients
2 kV class 3 serial link conforming to IEC 61000-4-4