All categories
Compare Cart

LU2B32B - Reversing power base, TeSys Ultra, 3P, 1NO + 1NC, 32A, 690VAC, 24VAC coil - Schneider Electric

Expected in 2-4 weeks
LU2B32B - Reversing power base, TeSys Ultra, 3P, 1NO + 1NC, 32A, 690VAC, 24VAC coil - Schneider Electric - Reversing power base, TeSys Ultra, 3P, 1NO + 1NC, 32A, 690VAC, 24VAC coil - Schneider Electric - 0
LU2B32B - Reversing power base, TeSys Ultra, 3P, 1NO + 1NC, 32A, 690VAC, 24VAC coil - Schneider Electric
436,09 €
436,09 € incl. VAT
Text About:
Reversing power base, TeSys Ultra, 3P, 1NO + 1NC, 32A, 690VAC, 24VAC coil - Schneider Electric
436,09 €
SPECIFICATIONS
Main
Device short name LU2B
Range TeSys
[uc] control circuit voltage 24 V AC 50/60 Hz
Product Name TeSys Ultra
[ui] rated insulation voltage 690 V conforming to IEC 60947-6-2 (pollution degree 3)
600 V conforming to UL 60947-4-1
600 V conforming to CSA C22.2 No 60947-4-1
Complementary
product compatibility Control unit LUC.X6B
Control unit LUC.1XB
Control unit LUC.05B
Control unit LUC.12B
Control unit LUC.18B
Control unit LUC.32B
[ie] rated operational current 28.5 A at <= 440 V
23 A at 500 V
21 A at 690 V
[ue] rated operational voltage 690 V AC for power circuit
compatibility code LU2B
[ics] rated service breaking capacity 50 kA at 230 V
50 kA at 440 V
10 kA at 500 V
4 kA at 690 V
[ith] conventional thermal current 32 A
Product certifications CE
UL
CSA
CCC
EAC
ASEFA
ATEX
Marine
Handle front plate colour 224 mm
Product or component type Reversing power base
tightening torque Control circuit: 0.8…1.2 N.m flat screwdriver 5 mm
Control circuit: 0.8…1.2 N.m Philips no 1 screwdriver 5 mm
Power circuit: 1.9…2.5 N.m flat screwdriver 6 mm
Power circuit: 1.9…2.5 N.m Philips No 2 screwdriver 6 mm
Power circuit: 1.9…2.5 N.m pozidriv No 2 screwdriver 6 mm
[uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-6-2
Auxiliary contact composition 1 NO + 1 NC
Connections - terminals Control circuit: screw clamp terminals 1 cable(s) 0.34…1.5 mm² flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 0.75…1.5 mm² flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 0.75…1.5 mm² rigid
Control circuit: screw clamp terminals 2 cable(s) 0.34…1.5 mm² flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 0.75…1.5 mm² flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 0.75…1.5 mm² rigid
Power circuit: screw clamp terminals 1 cable(s) 1…10 mm² rigid
Power circuit: screw clamp terminals 1 cable(s) 1…6 mm² flexible with cable end
Power circuit: screw clamp terminals 1 cable(s) 2.5…10 mm² flexible without cable end
Power circuit: screw clamp terminals 2 cable(s) 1…6 mm² flexible with cable end
Power circuit: screw clamp terminals 2 cable(s) 1…6 mm² rigid
Power circuit: screw clamp terminals 2 cable(s) 1.5…6 mm² flexible without cable end
Auxiliary contacts type type linked contacts (1 NO + 1 NC) conforming to IEC 60947-4-1
type mirror contact (1 NC) conforming to IEC 60947-1
Device application Motor control
Motor protection
Fixing mode Clipped (DIN rail)
Screw-fixed (plate)
Control circuit voltage limits 14.5 V AC drop-out
20...26.5 V AC in operation
width (w) 45 mm
network frequency 40...60 Hz
Heat dissipation 3 W for control circuit with LUCA, LUCB, LUCC, LUCD
1.8 W for control circuit with LUCM
Net weight 1.27 kg
Immunity to microbreaks 3 ms for control circuit
depth 126 mm
mechanical durability 15 Mcycles
Maximum operating rate 3600 cyc/h
operating time 150 ms with change of direction for power circuit
35 ms opening for control circuit
70 ms closing for control circuit
75 ms without change of direction for power circuit
Immunity to radioelectric fields 10 V conforming to IEC 61000-4-6
Inrush restraint duration 25 ms AC 50/60 Hz
Resistance to electrostatic discharge 8 kV level 3 in open air conforming to IEC 61000-4-2
8 kV level 4 on contact conforming to IEC 61000-4-2
Shock resistance 10 gn power poles open conforming to IEC 60068-2-27
15 gn power poles closed conforming to IEC 60068-2-27
Suitability for isolation Yes
Poles description 3P
Safe separation of circuit 400 V SELV between the control and auxiliary circuits conforming to IEC 60947-1 appendix N
400 V SELV between the control or auxiliary circuit and the main circuit conforming to IEC 60947-1 appendix N
Utilisation category AC-43
AC-44
AC-41
Typical current consumption 2360 mA at 24 V AC I maximum while closing
Safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Environment
Ambient air temp for storage/transportation -40…85 °C
ip degree of protection IP20 conforming to IEC 60947-1 (front panel and wired terminals)
IP20 conforming to IEC 60947-1 (other faces)
IP40 conforming to IEC 60947-1 (front panel outside connection zone)
operating altitude 2000 m
ambient air temperature for operation -25…60 °C with LUCM
-25…70 °C with LUCA, LUCB, LUCC, LUCD
Non-dissipating shock wave 1 kV serial mode conforming to IEC 60947-6-2
2 kV common mode conforming to IEC 60947-6-2
standards EN 60947-6-2
IEC 60947-6-2
UL 60947-4-1, with phase barrier
CSA C22.2 No 60947-4-1, with phase barrier
fire resistance 960 °C parts supporting live components conforming to IEC 60695-2-12
650 °C conforming to IEC 60695-2-12
immunity to voltage dips 70 % / 500 ms conforming to IEC 61000-4-11
resistance to radiated fields 10 V/m 3 conforming to IEC 61000-4-3
vibration resistance 2 gn (f= 5…300 Hz) power poles open conforming to IEC 60068-2-27
4 gn (f= 5…300 Hz) power poles closed conforming to IEC 60068-2-27
protective treatment TH conforming to IEC 60068
resistance to fast transients 2 kV class 3 serial link conforming to IEC 61000-4-4
4 kV class 4 all circuits except for serial link conforming to IEC 61000-4-4
Recently viewed
436,09 €
436,09 € incl. VAT
Expected in 2-4 weeks