All categories
Compare Cart

LTMR100PBD - Motor controller, TeSys T, Motor Management, Profibus DP, 6 logic inputs, 3 relay logic outputs, 5 to 100A, 24VDC - Schneider Electric

Expected in 2-4 weeks
LTMR100PBD - Motor controller, TeSys T, Motor Management, Profibus DP, 6 logic inputs, 3 relay logic outputs, 5 to 100A, 24VDC - Schneider Electric - Motor controller, TeSys T, Motor Management, Profibus DP, 6 logic inputs, 3 relay logic outputs, 5 to 100A, 24VDC - Schneider Electric - 0
LTMR100PBD - Motor controller, TeSys T, Motor Management, Profibus DP, 6 logic inputs, 3 relay logic outputs, 5 to 100A, 24VDC - Schneider Electric
957,62 € excl. VAT
1 168,30 € incl. VAT
Text About:
Motor controller, TeSys T, Motor Management, Profibus DP, 6 logic inputs, 3 relay logic outputs, 5 to 100A, 24VDC - Schneider Electric
1 168,30 €
SPECIFICATIONS
Main
Device short name LTMR
Measurement current 5…100 A
Range TeSys
Product Name TeSys T
[ui] rated insulation voltage 690 V conforming to EN/IEC 60947-1
690 V conforming to CSA C22.2 No 14
690 V conforming to UL 508
Complementary
compatibility code LTMR
Product certifications CSA
C-Tick
DNV
RMRoS
ATEX
EAC
RINA
CCC
KERI
GL
NOM
UL
LROS (Lloyds register of shipping)
ABS
BV
Connection pitch 5.08 mm
Handle front plate colour 61 mm
Product or component type Motor controller
tightening torque Control circuit: 0.5…0.6 N.m flat screwdriver 3 mm
[uimp] rated impulse withstand voltage 6 kV current or voltage measurement circuit conforming to EN/IEC 60947-4-1
0.8 kV communication circuit conforming to EN/IEC 60947-4-1
0.8 kV supply, inputs and outputs conforming to EN/IEC 60947-4-1
[us] rated supply voltage 24 V DC
Current consumption 56...127 mA
Connections - terminals Control circuit: connector 1 cable(s) 0.25…2.5 mm² (AWG 24...AWG 14) flexible with cable end
Control circuit: connector 1 cable(s) 0.2…2.5 mm² (AWG 24...AWG 14) flexible without cable end
Control circuit: connector 1 cable(s) 0.25…2.5 mm² (AWG 24...AWG 14) flexible without cable end
Control circuit: connector 1 cable(s) 0.2…2.5 mm² (AWG 24...AWG 14) solid without cable end
Control circuit: connector 2 cable(s) 0.2…1 mm² (AWG 24...AWG 14) flexible with cable end
Control circuit: connector 2 cable(s) 0.2…1.5 mm² (AWG 24...AWG 14) flexible without cable end
Control circuit: connector 2 cable(s) 0.5…1.5 mm² (AWG 24...AWG 14) flexible without cable end
Control circuit: connector 2 cable(s) 0.2…1 mm² (AWG 24...AWG 14) solid without cable end
current state 0 guaranteed Logic input: < 5 V and <= 15 mA for 5 ms
Associated fuse rating 4 A gG for output
0.5 A gG for control circuit
Bus type Profibus DP polarised 2-wire RS485 interface, addressing 1...125, transmission rate 9.6 kbit/s...12 Mbit/s, SUB-D 9 with 2 shielded twisted pairs, type A
Profibus DP polarised 2-wire RS485 interface, addressing 1...125, transmission rate 9.6 kbit/s...12 Mbit/s, terminal block with 2 shielded twisted pairs, type A
current state 1 guaranteed Logic input: < 15 V and 2...15 mA for 15 ms
Device application Equipment monitoring and control
Contacts type and composition 1 NO + 1 NC fault signal
3 NO
input current 7 mA
Load current 5 A at 250 V AC for logic output
5 A at 30 V DC for logic output
width (w) 91 mm
mechanical robustness Vibrations mounted on symmetrical rail: 1 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6
Vibrations plate mounted: 4 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6
Shocks half sine wave acceleration: 15 Gn for 11 ms conforming to EN/IEC 60068-2-27
supply voltage limits 20.4…26.24 V DC
Net weight 0.53 kg
measurement accuracy 5...15 % earth fault current internal measurement
1 % voltage (100...830 V)
3 % power factor
5 % earth fault current external measurement
+/- 30 min/year internal clock
0,02 temperature
5 % active and reactive power
0,02 current
communication port protocol Profibus DP
depth 122.5 mm
Pollution degree 3
Maximum operating rate 1800 cyc/h
Logic input number 6
Maximum output switching frequency 2 Hz
Metering type Imbalance current
Temperature
Average current Iavg
Phase current I1, I2, I3 RMS
Earth-fault current
Network and machine diagnosis type Trip context information
Event recording
Waiting time after overload tripping
Running hours counter/operating time
Remaining operating time before overload tripping
Fault recording
Motor control command recording
Trip history information
Phase fault and earth fault trip counters
Starting current and time
Permissible power 480 VA (AC-15), Ie = 2 A, 500000 cycles (output)
30 W (DC-13), Ie = 1.25 A, 500000 cycles (output)
Short-circuit withstand 100 kA conforming to EN/IEC 60947-4-1
Protection type Load fluctuation
Reverse polarity protection
Locked rotor
Thermal protection
Overload (long time)
Overload
Power factor variation
Earth-leakage protection
Thermal overload protection
Phase unbalance
Phase failure
Web services Web server
Environment
Ambient air temp for storage/transportation -40…80 °C
ip degree of protection IP20
operating altitude <= 2000 m without derating
ambient air temperature for operation -20…60 °C
electromagnetic compatibility Electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2
Radiated RF fields, 3, 10 V/m, conforming to EN/IEC 61000-4-3
Fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4
Fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4
Voltage dips and interruptions immunity test, 70 %, 500 ms, conforming to EN/IEC 61000-4-11
Conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6
Temperature sensor: surges (serial mode), 0.5 kV, conforming to EN/IEC 61000-4-5
Temperature sensor: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5
Control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5
Control circuit: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5
Communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5
Relay outputs and supply: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5
Relay outputs and supply: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5
overvoltage category III
standards CSA C22.2 No 14
EN 60947-4-1
IEC 60947-4-1
IACS E10
UL 508
fire resistance 650 °C conforming to EN/IEC 60695-2-12
960 °C conforming to UL 94
protective treatment 12 x 24 hour cycles conforming to EN/IEC 60068-2-30
48 h conforming to EN/IEC 60070-2-11
TH conforming to EN/IEC 60068
Recently viewed
957,62 € excl. VAT
1 168,30 € incl. VAT
Expected in 2-4 weeks