Device short name
LTMR
Measurement current
5…100 A
Range
TeSys
Product Name
TeSys T
[ui] rated insulation voltage
690 V conforming to EN/IEC 60947-1
690 V conforming to CSA C22.2 No 14
690 V conforming to UL 508
Complementary
compatibility code
LTMR
Product certifications
CSA
DNV
LROS (Lloyds register of shipping)
RINA
EAC
GL
UL
ATEX
BV
CCC
RMRoS
KERI
ABS
NOM
C-Tick
Connection pitch
5.08 mm
Handle front plate colour
61 mm
Product or component type
Motor controller
tightening torque
Control circuit: 0.5…0.6 N.m flat screwdriver 3 mm
[uimp] rated impulse withstand voltage
4 kV supply, inputs and outputs conforming to EN/IEC 60947-4-1
6 kV current or voltage measurement circuit conforming to EN/IEC 60947-4-1
0.8 kV communication circuit conforming to EN/IEC 60947-4-1
[us] rated supply voltage
100...240 V AC 50/60 Hz
Current consumption
8...62.8 mA
Connections - terminals
Control circuit: connector 1 cable(s) 0.25…2.5 mm² (AWG 24...AWG 14) flexible with cable end
Control circuit: connector 1 cable(s) 0.2…2.5 mm² (AWG 24...AWG 14) flexible without cable end
Control circuit: connector 1 cable(s) 0.25…2.5 mm² (AWG 24...AWG 14) flexible without cable end
Control circuit: connector 1 cable(s) 0.2…2.5 mm² (AWG 24...AWG 14) solid without cable end
Control circuit: connector 2 cable(s) 0.2…1 mm² (AWG 24...AWG 14) flexible with cable end
Control circuit: connector 2 cable(s) 0.2…1.5 mm² (AWG 24...AWG 14) flexible without cable end
Control circuit: connector 2 cable(s) 0.5…1.5 mm² (AWG 24...AWG 14) flexible without cable end
Control circuit: connector 2 cable(s) 0.2…1 mm² (AWG 24...AWG 14) solid without cable end
current state 0 guaranteed
Logic input: 0...40 V and <= 15 mA for 25 ms
Associated fuse rating
4 A gG for output
0.5 A gG for control circuit
Bus type
DeviceNet ISO 1198 interface, addressing 1...64, transmission rate 125...500 kbit/s, terminal block with 4 twisted shielded pairs cable
current state 1 guaranteed
Logic input: 79...264 V and >= 2 mA for 25 ms
Device application
Equipment monitoring and control
Contacts type and composition
1 NO + 1 NC fault signal
3 NO
input current
3.1 mA at 100 V
7.5 mA at 240 V
Load current
5 A at 250 V AC for logic output
5 A at 30 V DC for logic output
width (w)
91 mm
mechanical robustness
Vibrations mounted on symmetrical rail: 1 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6
Vibrations plate mounted: 4 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6
Shocks half sine wave acceleration: 15 Gn for 11 ms conforming to EN/IEC 60068-2-27
supply voltage limits
93.5…264 V AC
Net weight
0.53 kg
measurement accuracy
5...15 % earth fault current internal measurement
1 % voltage (100...830 V)
3 % power factor
5 % earth fault current external measurement
+/- 30 min/year internal clock
0,02 temperature
5 % active and reactive power
0,02 current
communication port protocol
DeviceNet
depth
122.5 mm
Pollution degree
3
Maximum operating rate
1800 cyc/h
Logic input number
6
Maximum output switching frequency
2 Hz
Metering type
Imbalance current
Temperature
Average current Iavg
Earth-fault current
Phase current I1, I2, I3 RMS
Network and machine diagnosis type
Motor control command recording
Trip history information
Running hours counter/operating time
Phase fault and earth fault trip counters
Remaining operating time before overload tripping
Fault recording
Trip context information
Event recording
Starting current and time
Waiting time after overload tripping
Permissible power
480 VA (AC-15), Ie = 2 A, 500000 cycles (output)
30 W (DC-13), Ie = 1.25 A, 500000 cycles (output)
Short-circuit withstand
100 kA conforming to EN/IEC 60947-4-1
Protection type
Phase failure
Overload (long time)
Load fluctuation
Thermal overload protection
Power factor variation
Overload
Locked rotor
Thermal protection
Earth-leakage protection
Phase unbalance
Reverse polarity protection
Web services
Web server
Environment
Ambient air temp for storage/transportation
-40…80 °C
ip degree of protection
IP20
operating altitude
<= 2000 m without derating
ambient air temperature for operation
-20…60 °C
electromagnetic compatibility
Electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2
Radiated RF fields, 3, 10 V/m, conforming to EN/IEC 61000-4-3
Fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4
Fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4
Voltage dips and interruptions immunity test, 70 %, 500 ms, conforming to EN/IEC 61000-4-11
Conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6
Temperature sensor: surges (serial mode), 0.5 kV, conforming to EN/IEC 61000-4-5
Temperature sensor: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5
Control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5
Communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5
Relay outputs and supply: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5
Relay outputs and supply: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5
Control circuit: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5
overvoltage category
III
standards
EN 60947-4-1
UL 508
IEC 60947-4-1
CSA C22.2 No 14
IACS E10
fire resistance
650 °C conforming to EN/IEC 60695-2-12
960 °C conforming to UL 94
protective treatment
12 x 24 hour cycles conforming to EN/IEC 60068-2-30
48 h conforming to EN/IEC 60070-2-11
TH conforming to EN/IEC 60068