Main
																					
												Device short name
												LTMR
											
                            
																					
												Measurement current
												5…100 A
											
                            
																					
												Range
												TeSys
											
                            
																					
												Product Name
												TeSys T
											
                            
																					
												[ui] rated insulation voltage
												690 V conforming to EN/IEC 60947-1
690 V conforming to CSA C22.2 No 14
690 V conforming to UL 508
											
                            
																			 
																	
										Complementary
																					
												compatibility code
												LTMR
											
                            
																					
												Product certifications
												LROS (Lloyds register of shipping)
DNV
UL
EAC
GL
CCC
BV
ABS
KERI
ATEX
NOM
RINA
RMRoS
C-Tick
CSA
											
                            
																					
												Connection pitch
												5.08 mm
											
                            
																					
												Handle front plate colour
												61 mm
											
                            
																					
												Product or component type
												Motor controller
											
                            
																					
												tightening torque
												Control circuit: 0.5…0.6 N.m flat screwdriver 3 mm
											
                            
																					
												[uimp] rated impulse withstand voltage
												4 kV supply, inputs and outputs conforming to EN/IEC 60947-4-1
6 kV current or voltage measurement circuit conforming to EN/IEC 60947-4-1
0.8 kV communication circuit conforming to EN/IEC 60947-4-1
											
                            
																					
												[us] rated supply voltage
												100...240 V AC 50/60 Hz
											
                            
																					
												Current consumption
												8...62.8 mA
											
                            
																					
												Connections - terminals
												Control circuit: connector 1 cable(s) 0.25…2.5 mm² (AWG 24...AWG 14) flexible with cable end
Control circuit: connector 1 cable(s) 0.2…2.5 mm² (AWG 24...AWG 14) flexible without cable end
Control circuit: connector 1 cable(s) 0.25…2.5 mm² (AWG 24...AWG 14) flexible without cable end
Control circuit: connector 1 cable(s) 0.2…2.5 mm² (AWG 24...AWG 14) solid without cable end
Control circuit: connector 2 cable(s) 0.2…1 mm² (AWG 24...AWG 14) flexible with cable end
Control circuit: connector 2 cable(s) 0.2…1.5 mm² (AWG 24...AWG 14) flexible without cable end
Control circuit: connector 2 cable(s) 0.5…1.5 mm² (AWG 24...AWG 14) flexible without cable end
Control circuit: connector 2 cable(s) 0.2…1 mm² (AWG 24...AWG 14) solid without cable end
											
                            
																					
												current state 0 guaranteed
												Logic input: 0...40 V and <= 15 mA for 25 ms
											
                            
																					
												Associated fuse rating
												4 A gG for output
0.5 A gG for control circuit
											
                            
																					
												Bus type
												CANopen ISO 1198 interface, addressing 1...127, transmission rate 10...1000 kbit/s, SUB-D 9 with 4 twisted shielded pairs cable
CANopen ISO 1198 interface, addressing 1...127, transmission rate 10...1000 kbit/s, terminal block with 4 twisted shielded pairs cable
											
                            
																					
												current state 1 guaranteed
												Logic input: 79...264 V and >= 2 mA for 25 ms
											
                            
																					
												Device application
												Equipment monitoring and control
											
                            
																					
												Contacts type and composition
												1 NO + 1 NC fault signal
3 NO
											
                            
																					
												input current
												3.1 mA at 100 V
7.5 mA at 240 V
											
                            
																					
												Load current
												5 A at 250 V AC for logic output
5 A at 30 V DC for logic output
											
                            
																					
												width (w)
												91 mm
											
                            
																					
												mechanical robustness
												Vibrations mounted on symmetrical rail: 1 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6
Vibrations plate mounted: 4 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6
Shocks half sine wave acceleration: 15 Gn for 11 ms conforming to EN/IEC 60068-2-27
											
                            
																					
												supply voltage limits
												93.5…264 V AC
											
                            
																					
												Net weight
												0.53 kg
											
                            
																					
												measurement accuracy
												5...15 % earth fault current internal measurement
1 % voltage (100...830 V)
3 % power factor
5 % earth fault current external measurement
+/- 30 min/year internal clock
0,02 temperature
5 % active and reactive power
0,02 current
											
                            
																					
												communication port protocol
												CANopen
											
                            
																					
												depth
												122.5 mm
											
                            
																					
												Pollution degree
												3
											
                            
																					
												Maximum operating rate
												1800 cyc/h
											
                            
																					
												Logic input number
												6
											
                            
																					
												Maximum output switching frequency
												2 Hz
											
                            
																					
												Metering type
												Earth-fault current
Phase current I1, I2, I3 RMS
Imbalance current
Temperature
Average current Iavg
											
                            
																					
												Network and machine diagnosis type
												Event recording
Trip history information
Starting current and time
Running hours counter/operating time
Motor control command recording
Remaining operating time before overload tripping
Fault recording
Phase fault and earth fault trip counters
Waiting time after overload tripping
Trip context information
											
                            
																					
												Permissible power
												480 VA (AC-15), Ie = 2 A, 500000 cycles (output)
30 W (DC-13), Ie = 1.25 A, 500000 cycles (output)
											
                            
																					
												Short-circuit withstand
												100 kA conforming to EN/IEC 60947-4-1
											
                            
																					
												Protection type
												Thermal protection
Locked rotor
Phase failure
Earth-leakage protection
Overload (long time)
Power factor variation
Phase unbalance
Load fluctuation
Thermal overload protection
Reverse polarity protection
Overload
											
                            
																					
												Web services
												Web server
											
                            
																			 
																	
										Environment
																					
												Ambient air temp for storage/transportation
												-40…80 °C
											
                            
																					
												ip degree of protection
												IP20
											
                            
																					
												operating altitude
												<= 2000 m without derating
											
                            
																					
												ambient air temperature for operation
												-20…60 °C
											
                            
																					
												electromagnetic compatibility
												Electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2
Radiated RF fields, 3, 10 V/m, conforming to EN/IEC 61000-4-3
Fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4
Fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4
Voltage dips and interruptions immunity test, 70 %, 500 ms, conforming to EN/IEC 61000-4-11
Conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6
Temperature sensor: surges (serial mode), 0.5 kV, conforming to EN/IEC 61000-4-5
Temperature sensor: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5
Control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5
Communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5
Relay outputs and supply: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5
Relay outputs and supply: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5
Control circuit: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5
											
                            
																					
												overvoltage category
												III
											
                            
																					
												standards
												IEC 60947-4-1
CSA C22.2 No 14
IACS E10
EN 60947-4-1
UL 508
											
                            
																					
												fire resistance
												650 °C conforming to EN/IEC 60695-2-12
960 °C conforming to UL 94
											
                            
																					
												protective treatment
												12 x 24 hour cycles conforming to EN/IEC 60068-2-30
48 h conforming to EN/IEC 60070-2-11
TH conforming to EN/IEC 60068