Main
Device short name
LTMR
Measurement current
0.4…8 A
Range
TeSys
Product Name
TeSys T
[ui] rated insulation voltage
690 V conforming to EN/IEC 60947-1
690 V conforming to CSA C22.2 No 14
690 V conforming to UL 508
Complementary
compatibility code
LTMR
Product certifications
CSA
C-Tick
UL
CCC
LROS (Lloyds register of shipping)
NOM
ABS
GL
EAC
BV
DNV
RINA
RMRoS
ATEX
KERI
Connection pitch
5.08 mm
Handle front plate colour
61 mm
Product or component type
Motor controller
tightening torque
Control circuit: 0.5…0.6 N.m flat screwdriver 3 mm
[uimp] rated impulse withstand voltage
4 kV supply, inputs and outputs conforming to EN/IEC 60947-4-1
6 kV current or voltage measurement circuit conforming to EN/IEC 60947-4-1
0.8 kV communication circuit conforming to EN/IEC 60947-4-1
[us] rated supply voltage
100...240 V AC 50/60 Hz
Current consumption
8...62.8 mA
Connections - terminals
Control circuit: connector 1 cable(s) 0.25…2.5 mm² (AWG 24...AWG 14) flexible with cable end
Control circuit: connector 1 cable(s) 0.2…2.5 mm² (AWG 24...AWG 14) flexible without cable end
Control circuit: connector 1 cable(s) 0.25…2.5 mm² (AWG 24...AWG 14) flexible without cable end
Control circuit: connector 1 cable(s) 0.2…2.5 mm² (AWG 24...AWG 14) solid without cable end
Control circuit: connector 2 cable(s) 0.2…1 mm² (AWG 24...AWG 14) flexible with cable end
Control circuit: connector 2 cable(s) 0.2…1.5 mm² (AWG 24...AWG 14) flexible without cable end
Control circuit: connector 2 cable(s) 0.5…1.5 mm² (AWG 24...AWG 14) flexible without cable end
Control circuit: connector 2 cable(s) 0.2…1 mm² (AWG 24...AWG 14) solid without cable end
current state 0 guaranteed
Logic input: 0...40 V and <= 15 mA for 25 ms
Associated fuse rating
4 A gG for output
0.5 A gG for control circuit
Bus type
Profibus DP polarised 2-wire RS485 interface, addressing 1...125, transmission rate 9.6 kbit/s...12 Mbit/s, SUB-D 9 with 2 shielded twisted pairs, type A
Profibus DP polarised 2-wire RS485 interface, addressing 1...125, transmission rate 9.6 kbit/s...12 Mbit/s, terminal block with 2 shielded twisted pairs, type A
current state 1 guaranteed
Logic input: 79...264 V and >= 2 mA for 25 ms
Device application
Equipment monitoring and control
Contacts type and composition
1 NO + 1 NC fault signal
3 NO
input current
3.1 mA at 100 V
7.5 mA at 240 V
Load current
5 A at 250 V AC for logic output
5 A at 30 V DC for logic output
width (w)
91 mm
mechanical robustness
Vibrations mounted on symmetrical rail: 1 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6
Vibrations plate mounted: 4 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6
Shocks half sine wave acceleration: 15 Gn for 11 ms conforming to EN/IEC 60068-2-27
supply voltage limits
93.5…264 V AC
Net weight
0.53 kg
measurement accuracy
5...15 % earth fault current internal measurement
1 % voltage (100...830 V)
3 % power factor
5 % earth fault current external measurement
+/- 30 min/year internal clock
0,02 temperature
1 % current
5 % active and reactive power
communication port protocol
Profibus DP
depth
122.5 mm
Pollution degree
3
Maximum operating rate
1800 cyc/h
Logic input number
6
Maximum output switching frequency
2 Hz
Metering type
Average current Iavg
Earth-fault current
Temperature
Imbalance current
Phase current I1, I2, I3 RMS
Network and machine diagnosis type
Phase fault and earth fault trip counters
Trip history information
Starting current and time
Fault recording
Waiting time after overload tripping
Event recording
Motor control command recording
Running hours counter/operating time
Trip context information
Remaining operating time before overload tripping
Permissible power
480 VA (AC-15), Ie = 2 A, 500000 cycles (output)
30 W (DC-13), Ie = 1.25 A, 500000 cycles (output)
Short-circuit withstand
100 kA conforming to EN/IEC 60947-4-1
Protection type
Locked rotor
Overload
Phase unbalance
Phase failure
Earth-leakage protection
Reverse polarity protection
Load fluctuation
Thermal protection
Power factor variation
Thermal overload protection
Overload (long time)
Web services
Web server
Environment
Ambient air temp for storage/transportation
-40…80 °C
ip degree of protection
IP20
operating altitude
<= 2000 m without derating
ambient air temperature for operation
-20…60 °C
electromagnetic compatibility
Electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2
Radiated RF fields, 3, 10 V/m, conforming to EN/IEC 61000-4-3
Fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4
Fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4
Voltage dips and interruptions immunity test, 70 %, 500 ms, conforming to EN/IEC 61000-4-11
Conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6
Temperature sensor: surges (serial mode), 0.5 kV, conforming to EN/IEC 61000-4-5
Temperature sensor: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5
Control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5
Communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5
Relay outputs and supply: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5
Relay outputs and supply: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5
Control circuit: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5
overvoltage category
III
standards
UL 508
IEC 60947-4-1
EN 60947-4-1
IACS E10
CSA C22.2 No 14
fire resistance
650 °C conforming to EN/IEC 60695-2-12
960 °C conforming to UL 94
protective treatment
12 x 24 hour cycles conforming to EN/IEC 60068-2-30
48 h conforming to EN/IEC 60070-2-11
TH conforming to EN/IEC 60068