Main
Device short name
LTME
Range
TeSys
Product Name
TeSys T
[ui] rated insulation voltage
690 V conforming to EN/IEC 60947-1
690 V conforming to CSA C22.2 No 14
690 V conforming to UL 508
Complementary
compatibility code
LTME
range compatibility
TeSys (TeSys T) LTMR motor controller
Product certifications
LROS (Lloyds register of shipping)
ATEX
NOM
EAC
RMRoS
GL
UL
DNV
BV
RINA
KERI
C-Tick
CSA
CCC
ABS
Connection pitch
5.08 mm
Handle front plate colour
61 mm
Product or component type
Extension module
tightening torque
Control circuit: 0.5…0.6 N.m flat screwdriver 3 mm
[uimp] rated impulse withstand voltage
4 kV supply, inputs and outputs conforming to EN/IEC 60947-4-1
6 kV current or voltage measurement circuit conforming to EN/IEC 60947-4-1
Connections - terminals
Control circuit: connector 1 cable(s) 0.25…2.5 mm² (AWG 24...AWG 14) flexible with cable end
Control circuit: connector 1 cable(s) 0.2…2.5 mm² (AWG 24...AWG 14) flexible without cable end
Control circuit: connector 1 cable(s) 0.25…2.5 mm² (AWG 24...AWG 14) flexible without cable end
Control circuit: connector 1 cable(s) 0.2…2.5 mm² (AWG 24...AWG 14) solid without cable end
Control circuit: connector 2 cable(s) 0.2…1 mm² (AWG 24...AWG 14) flexible with cable end
Control circuit: connector 2 cable(s) 0.2…1.5 mm² (AWG 24...AWG 14) flexible without cable end
Control circuit: connector 2 cable(s) 0.5…1.5 mm² (AWG 24...AWG 14) flexible without cable end
Control circuit: connector 2 cable(s) 0.2…1 mm² (AWG 24...AWG 14) solid without cable end
current state 0 guaranteed
Logic input: 0...40 V and 2...15 mA for 25 ms
current state 1 guaranteed
Logic input: 79...264 V and <= 15 mA for 25 ms
Device application
Equipment monitoring and control
Contacts type and composition
Without
input current
3.1 mA at 100 V
7.5 mA at 240 V
width (w)
45 mm
mechanical robustness
Shocks half sine wave acceleration: 15 Gn for 11 ms conforming to EN/IEC 60068-2-27
Vibrations mounted on symmetrical rail: 1 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6
Vibrations plate mounted: 4 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6
Net weight
0.21 kg
measurement accuracy
1 % voltage (100...830 V)
3 % power factor
5 % active and reactive power
depth
120.7 mm
Pollution degree
3
Maximum operating rate
1800 cyc/h
Logic input number
4
Maximum output switching frequency
2 Hz
Metering type
Imbalance voltage
Active power P, P1, P2, P3
Calculated active and reactive energy (+/- W.h, +/- VAR.h)
Voltage U21, U32, U13, V1, V2, V3
Reactive power Q, Q1, Q2, Q3
Frequency
Power factor
Supply
Via the controller
Environment
Ambient air temp for storage/transportation
-40…80 °C
ip degree of protection
IP20
operating altitude
<= 2000 m without derating
ambient air temperature for operation
-20…60 °C
electromagnetic compatibility
Electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2
Fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4
Fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4
Conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6
Control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5
Communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5
Voltage inputs: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5
Voltage inputs: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5
Control circuit: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5
overvoltage category
III
standards
CSA C22.2 No 14
IACS E10
IEC 60947-4-1
UL 508
EN 60947-4-1
fire resistance
650 °C conforming to EN/IEC 60695-2-12
960 °C conforming to UL 94
protective treatment
12 x 24 hour cycles conforming to EN/IEC 60068-2-30
48 h conforming to EN/IEC 60070-2-11
TH conforming to EN/IEC 60068