All categories
Compare Cart

LRD106 - Thermal overload relay,TeSys Deca,4-6A,1NO+1NC,class 10A,lugs ring terminal - Schneider Electric

Expected in 2-4 weeks
LRD106 - Thermal overload relay,TeSys Deca,4-6A,1NO+1NC,class 10A,lugs ring terminal - Schneider Electric - Thermal overload relay,TeSys Deca,4-6A,1NO+1NC,class 10A,lugs ring terminal - Schneider Electric - 0
LRD106 - Thermal overload relay,TeSys Deca,4-6A,1NO+1NC,class 10A,lugs ring terminal - Schneider Electric
64,40 € excl. VAT
78,56 € incl. VAT
Text About:
Thermal overload relay,TeSys Deca,4-6A,1NO+1NC,class 10A,lugs ring terminal - Schneider Electric
78,56 €
SPECIFICATIONS
Main
Device short name LRD
Range TeSys
TeSys Deca
thermal overload class Class 10A conforming to IEC 60947-4-1
Product Name TeSys LRD
TeSys Deca
[ui] rated insulation voltage Power circuit: 600 V conforming to CSA
Power circuit: 600 V conforming to UL
Power circuit: 690 V conforming to IEC 60947-4-1
Relay application Motor protection
thermal protection adjustment range 4…6 A
Complementary
product compatibility LC1D32
LC1D18
LC1D25
LC1D12
LC1D09
LC1D38
[ue] rated operational voltage 690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1
[ith] conventional thermal current 5 A for signalling circuit
Control type Red push-button: stop
Blue push-button: reset
Product certifications IEC
UL
CSA
CCC
EAC
BV
RINA
DNV-GL
LROS (Lloyds register of shipping)
ATEX INERIS
UKCA
Connection pitch 14.5 mm
Handle front plate colour 66 mm
Product or component type Differential thermal overload relay
tightening torque Control circuit: 1.7 N.m - on screw clamp terminals
Power circuit: 2.3 N.m - on lugs-ring terminals M4
[uimp] rated impulse withstand voltage 6 kV
Auxiliary contact composition 1 NO + 1 NC
temperature compensation -20…60 °C
Connections - terminals Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² solid without cable end
Power circuit: lugs-ring terminals
Associated fuse rating 4 A gG for signalling circuit
4 A BS for signalling circuit
Permissible current 3 A at 120 V AC-15 for signalling circuit
0.22 A at 125 V DC-13 for signalling circuit
width (w) 45 mm
mechanical robustness Vibrations: 6 Gn conforming to IEC 60068-2-6
Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7
network frequency 0...400 Hz
Flame retardance V1 conforming to UL 94
Net weight 0.124 kg
Mounting support Plate, with specific accessories
Rail, with specific accessories
Under contactor
depth 70 mm
Network type AC
DC
dielectric strength 1.89 kV at 50 Hz conforming to IEC 60947-1
Phase failure sensitivity Tripping current 130 % of Ir on two phase, the last one at 0
Tripping threshold 1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
Environment
Ambient air temp for storage/transportation -60…70 °C
Climatic withstand conforming to IACS E10
ip degree of protection IP20 conforming to IEC 60529
ambient air temperature for operation -20…60 °C without derating conforming to IEC 60947-4-1
standards EN/IEC 60947-4-1
EN/IEC 60947-5-1
UL 60947-4-1
UL 60947-5-1
CSA C22.2 No 60947-4-1
CSA C22.2 No 60947-5-1
GB/T 14048.4
GB/T 14048.5
EN 50495
Recently viewed
64,40 € excl. VAT
78,56 € incl. VAT
Expected in 2-4 weeks