All categories
Compare Cart

LR97D015M7 - Electronic overload relay for motor TeSys 0.3...1.5 A 200...240 V AC - Schneider Electric

Expected in 2-4 weeks
LR97D015M7 - Electronic overload relay for motor TeSys 0.3...1.5 A 200...240 V AC - Schneider Electric - Electronic overload relay for motor TeSys 0.3...1.5 A 200...240 V AC - Schneider Electric - 0
LR97D015M7 - Electronic overload relay for motor TeSys 0.3...1.5 A 200...240 V AC - Schneider Electric
106,27 €
106,27 € incl. VAT
Text About:
Electronic overload relay for motor TeSys 0.3...1.5 A 200...240 V AC - Schneider Electric
106,27 €
SPECIFICATIONS
Main
Device short name LR97
Range TeSys
Product Name TeSys D
[ui] rated insulation voltage Power circuit: 600 V conforming to CSA
Power circuit: 600 V conforming to UL
Power circuit: 690 V conforming to IEC 60947-4-1
reset Automatic reset 120 s fixed
Electrical by interruption of power supply for minimum 0.1 s
Manual reset
Relay application Sensitivity to phase failure
Overload Imax > Isetting
Locked rotor, mechanical jamming I > 3 x Isetting
thermal protection adjustment range 0.3…1.5 A
Complementary
product compatibility LC1D09...D38
[ue] rated operational voltage 600 V AC 50/60 Hz for power circuit conforming to CSA
600 V AC 50/60 Hz for power circuit conforming to UL
690 V AC 50/60 Hz for power circuit conforming to IEC 60947-4-1
[ith] conventional thermal current 3 A for control circuit
Product certifications CSA
UL
GOST
Handle front plate colour 67.5 mm
Product or component type Electronic overcurrent relay
tightening torque Control circuit: 0.6...1.2 N.m on lug-clamp
Power circuit: 2 N.m on cable
[uimp] rated impulse withstand voltage 6 kV
[us] rated supply voltage 200...240 V AC
Connections - terminals Control circuit: cable 1 x 1…25 mm²flexible with cable end
Control circuit: cable 1 x 1…25 mm²flexible without cable end
Power circuit: cable 1 x 1…4 mm²flexible with cable end
Power circuit: cable 1 x 1.5…10 mm²flexible without cable end
Power circuit: lug-clamp 1 x 1…4 mm²flexible with cable end
Power circuit: lug-clamp 1 x 1.5…10 mm²flexible without cable end
Control circuit: cable 2 x 1…25 mm²flexible with cable end
Control circuit: cable 2 x 1…25 mm²flexible without cable end
Control circuit: lug-clamp 1 x 1…25 mm²flexible with cable end
Control circuit: lug-clamp 1 x 1…25 mm²flexible without cable end
Control circuit: lug-clamp 2 x 1…25 mm²flexible with cable end
Control circuit: lug-clamp 2 x 1…25 mm²flexible without cable end
Quantity per set Set of 10
time range 0.2...10 s - O-time knob
0.3...10 s - O-time knob
0.5..30 s - D-time knob
Contacts type and composition 1 C/O
width (w) 45 mm
network frequency 50...60 Hz
Disturbance radiated/conducted 10 V conforming to EN 61000-4-6
Class A conforming to EN 55011
maximum power 28 W at 110 V DC conforming to IEC 60947
28 W at 220 V DC conforming to IEC 60947
55 W at 24 V DC conforming to IEC 60947
55 W at 48 V DC conforming to IEC 60947
140 VA at 48 V AC conforming to IEC 60947
360 VA at 110 V AC conforming to IEC 60947
360 VA at 220 V AC conforming to IEC 60947
70 VA at 24 V AC conforming to IEC 60947
Net weight 0.172 kg
Mounting support Direct on contactor
Rail
depth 67.5 mm
Network type AC
dielectric strength 2 V 50 Hz conforming to IEC 60255-5
Signalling function 2 LEDs
Phase failure sensitivity < 3 s
Tripping threshold 0.3...1.3 A
Resistance to electrostatic discharge 6 kV in indirect mode
8 kV in air
Shock resistance 15 gn 11 ms conforming to IEC 60068-2-7
Surge withstand 6 kV conforming to IEC 61000-4-5
Protection type BS fuse 3 A - for control circuit
GB2 circuit breaker 3 A - for control circuit
GG fuse 3 A - for control circuit
Environment
Ambient air temp for storage/transportation -30…80 °C
ip degree of protection IP20 conforming to IEC 60529
operating altitude 2000 m
ambient air temperature for operation -25…60 °C conforming to IEC 60947-4-1
standards IEC 60255-6
IEC 60947
fire resistance 850 °C conforming to IEC 60695-2-1
resistance to radiated fields 10 V/m level 3
vibration resistance 4 gn conforming to IEC 60068-2-6
protective treatment TH conforming to IEC 60068
resistance to fast transients 2 kV
Recently viewed