Complementary
[ie] rated operational current
6 A at <= 440 V AC AC-3 for power circuit
6 A at <= 440 V AC AC-3e for power circuit
[ue] rated operational voltage
Power circuit: 690 V AC 50/60 Hz
Signalling circuit: <= 690 V AC 50/60 Hz
[ics] rated service breaking capacity
110 A at 415 V conforming to IEC 60947
110 A at 440 V conforming to IEC 60947
80 A at 500 V conforming to IEC 60947
110 A at 220...230 V conforming to IEC 60947
110 A at 380...400 V conforming to IEC 60947
70 A at 660...690 V conforming to IEC 60947
[ith] conventional thermal current
20 A (at 50 °C) for power circuit
10 A (at 50 °C) for signalling circuit
Product certifications
CB Scheme
CCC
UL
CSA
EAC
CE
UKCA
Handle front plate colour
58 mm
Product or component type
Contactor
tightening torque
0.8…1.3 N.m - on screw clamp terminals Philips No 2
0.8…1.3 N.m - on screw clamp terminals flat Ø 6 mm
0.8…1.3 N.m - on screw clamp terminals pozidriv No 2
[uimp] rated impulse withstand voltage
8 kV
Auxiliary contact composition
1 NO
minimum switching current
5 mA for signalling circuit
Associated fuse rating
25 A gG at <= 440 V for power circuit
25 A aM for power circuit
10 A gG for signalling circuit conforming to IEC 60947
10 A gG for signalling circuit conforming to VDE 0660
Auxiliary contacts type
type instantaneous 1 NO
Control circuit voltage limits
Operational: 0.8...1.15 Uc (at <50 °C)
Drop-out: 0.1...0.75 Uc (at <50 °C)
width (w)
45 mm
Flame retardance
V1 conforming to UL 94
Requirement 2 conforming to NF F 16-101
Requirement 2 conforming to NF F 16-102
Net weight
0.225 kg
Hold-in power consumption in w
3 W at 20 °C
Mounting support
Plate
Rail
depth
57 mm
inrush power in w
3 W (at 20 °C)
mechanical durability
10 Mcycles
Irms rated making capacity
110 A AC for power circuit conforming to NF C 63-110
110 A AC for power circuit conforming to IEC 60947
110 A AC for signalling circuit conforming to IEC 60947
Maximum operating rate
3600 cyc/h
operating time
30...40 ms coil energisation and NO closing
10 ms coil de-energisation and NO opening
minimum switching voltage
17 V for signalling circuit
Pole contact composition
3 NO
Poles description
3P
Utilisation category
AC-4
AC-3
AC-3e
Safety reliability level
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Environment
Ambient air temp for storage/transportation
-50…80 °C
operating altitude
2000 m without derating
Range of product
TeSys K
ambient air temperature for operation
-25…50 °C
overvoltage category
III
standards
EN/IEC 60947-4-1
GB/T 14048.4
UL 60947-4-1
CSA C22.2 No 60947-4-1
JIS C8201-4-1
insulation resistance
> 10 MOhm for signalling circuit