SPECIFICATIONS
Main
Contactor application Resistive load
Device short name LP1D
Range TeSys
[uc] control circuit voltage 24 V DC
[ui] rated insulation voltage Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Power circuit: 1000 V conforming to IEC 60947-4-1
control circuit type DC DC standard
average impedance 0.8 mOhm - Ith 125 A 50 Hz for power circuit
Complementary
[ie] rated operational current 125 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
[ue] rated operational voltage Power circuit: <= 690 V AC 25...400 Hz
compatibility code LP1D
[ics] rated service breaking capacity 1100 A at 440 V for power circuit conforming to IEC 60947
[icw] rated short-time withstand current 135 A 40 °C - 10 min for power circuit
320 A 40 °C - 1 min for power circuit
640 A 40 °C - 10 s for power circuit
990 A 40 °C - 1 s for power circuit
[ith] conventional thermal current 125 A (at 60 °C) for power circuit
Product certifications UL
CSA
CCC
EAC
UKCA
CB
DNV-GL
RINA
BV
LROS (Lloyds register of shipping)
Handle front plate colour 127 mm
Product or component type Contactor
tightening torque Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
Power circuit: 12 N.m - on connector - with screwdriver flat Ø 6 to Ø 8 mm
Power circuit: 12 N.m - on connector hexagonal screw head 4 mm
Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
[uimp] rated impulse withstand voltage 8 kV conforming to IEC 60947
Connections - terminals Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid
Power circuit: connector 1 4…50 mm² - cable stiffness: flexible without cable end
Power circuit: connector 2 4…25 mm² - cable stiffness: flexible without cable end
Power circuit: connector 1 4…50 mm² - cable stiffness: flexible with cable end
Power circuit: connector 2 4…16 mm² - cable stiffness: flexible with cable end
Power circuit: connector 1 4…50 mm² - cable stiffness: solid
Power circuit: connector 2 4…25 mm² - cable stiffness: solid
Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible with cable end
Associated fuse rating 200 A gG at <= 690 V coordination type 1 for power circuit
160 A gG at <= 690 V coordination type 2 for power circuit
contact compatibility M4
Control circuit voltage limits 0.1...0.3 Uc (-40…55 °C):drop-out DC
0.85...1.1 Uc (-40…55 °C):operational DC
width (w) 96 mm
mechanical robustness Vibrations contactor open (2 Gn, 5...300 Hz)
Vibrations contactor closed (3 Gn, 5...300 Hz)
Shocks contactor open (8 Gn for 11 ms)
Shocks contactor closed (10 Gn for 11 ms)
Flame retardance V1 conforming to UL 94
Net weight 2.91 kg
time constant 75 ms
Hold-in power consumption in w 22 W at 20 °C
Mounting support Plate
Rail
power dissipation per pole 12.5 W AC-1
depth 196 mm
inrush power in w 22 W (at 20 °C)
mechanical durability 10 Mcycles
electrical durability 0.8 Mcycles 125 A AC-1 at Ue <= 440 V
Irms rated making capacity 1100 A at 440 V for power circuit conforming to IEC 60947
Pollution degree 3
Maximum operating rate 3600 cyc/h 60 °C
operating time 6...20 ms opening
20...35 ms closing
Protective cover Without
coil technology Without built-in suppressor module
Pole contact composition 2 NO + 2 NC
Poles description 4P
Utilisation category AC-1
Safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Environment
ip degree of protection IP20 front face conforming to IEC 60529
operating altitude 0...3000 m
Permissible ambient air temperature around the device -40…60 °C
60…70 °C with derating
Range of product TeSys Deca
overvoltage category III
standards CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
fire resistance 850 °C conforming to IEC 60695-2-1