Main
Contactor application
Resistive load
Device short name
LP1D
Range
TeSys
[uc] control circuit voltage
24 V DC
[ui] rated insulation voltage
Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Power circuit: 1000 V conforming to IEC 60947-4-1
control circuit type
DC DC standard
average impedance
0.8 mOhm - Ith 125 A 50 Hz for power circuit
Complementary
[ie] rated operational current
125 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
[ue] rated operational voltage
Power circuit: <= 690 V AC 25...400 Hz
compatibility code
LP1D
[ics] rated service breaking capacity
1100 A at 440 V for power circuit conforming to IEC 60947
[icw] rated short-time withstand current
135 A 40 °C - 10 min for power circuit
320 A 40 °C - 1 min for power circuit
640 A 40 °C - 10 s for power circuit
990 A 40 °C - 1 s for power circuit
[ith] conventional thermal current
125 A (at 60 °C) for power circuit
Product certifications
UL
CSA
CCC
EAC
UKCA
CB
DNV-GL
RINA
BV
LROS (Lloyds register of shipping)
Handle front plate colour
127 mm
Product or component type
Contactor
tightening torque
Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
Power circuit: 12 N.m - on connector - with screwdriver flat Ø 6 to Ø 8 mm
Power circuit: 12 N.m - on connector hexagonal screw head 4 mm
Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
[uimp] rated impulse withstand voltage
8 kV conforming to IEC 60947
Connections - terminals
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid
Power circuit: connector 1 4…50 mm² - cable stiffness: flexible without cable end
Power circuit: connector 2 4…25 mm² - cable stiffness: flexible without cable end
Power circuit: connector 1 4…50 mm² - cable stiffness: flexible with cable end
Power circuit: connector 2 4…16 mm² - cable stiffness: flexible with cable end
Power circuit: connector 1 4…50 mm² - cable stiffness: solid
Power circuit: connector 2 4…25 mm² - cable stiffness: solid
Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible with cable end
Associated fuse rating
200 A gG at <= 690 V coordination type 1 for power circuit
160 A gG at <= 690 V coordination type 2 for power circuit
contact compatibility
M4
Control circuit voltage limits
0.1...0.3 Uc (-40…55 °C):drop-out DC
0.85...1.1 Uc (-40…55 °C):operational DC
width (w)
96 mm
mechanical robustness
Vibrations contactor open (2 Gn, 5...300 Hz)
Vibrations contactor closed (3 Gn, 5...300 Hz)
Shocks contactor open (8 Gn for 11 ms)
Shocks contactor closed (10 Gn for 11 ms)
Flame retardance
V1 conforming to UL 94
Net weight
2.91 kg
time constant
75 ms
Hold-in power consumption in w
22 W at 20 °C
Mounting support
Plate
Rail
power dissipation per pole
12.5 W AC-1
depth
196 mm
inrush power in w
22 W (at 20 °C)
mechanical durability
10 Mcycles
electrical durability
0.8 Mcycles 125 A AC-1 at Ue <= 440 V
Irms rated making capacity
1100 A at 440 V for power circuit conforming to IEC 60947
Pollution degree
3
Maximum operating rate
3600 cyc/h 60 °C
operating time
6...20 ms opening
20...35 ms closing
Protective cover
Without
coil technology
Without built-in suppressor module
Pole contact composition
2 NO + 2 NC
Poles description
4P
Utilisation category
AC-1
Safety reliability level
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Environment
ip degree of protection
IP20 front face conforming to IEC 60529
operating altitude
0...3000 m
Permissible ambient air temperature around the device
-40…60 °C
60…70 °C with derating
Range of product
TeSys Deca
overvoltage category
III
standards
CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
fire resistance
850 °C conforming to IEC 60695-2-1