Main
Contactor application
Resistive load
Device short name
LP1D
Range
TeSys
[uc] control circuit voltage
24 V DC
[ui] rated insulation voltage
Power circuit: 690 V conforming to IEC 60947-4-1
Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
control circuit type
DC DC standard
average impedance
1.5 mOhm - Ith 60 A 50 Hz for power circuit
Complementary
[ie] rated operational current
60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
[ue] rated operational voltage
Power circuit: <= 1000 V AC 25...400 Hz
compatibility code
LP1D
[ics] rated service breaking capacity
800 A at 440 V for power circuit conforming to IEC 60947
[icw] rated short-time withstand current
72 A 40 °C - 10 min for power circuit
165 A 40 °C - 1 min for power circuit
320 A 40 °C - 10 s for power circuit
720 A 40 °C - 1 s for power circuit
[ith] conventional thermal current
60 A (at 60 °C) for power circuit
Product certifications
UL
CSA
CCC
EAC
UKCA
CB
DNV-GL
RINA
BV
LROS (Lloyds register of shipping)
Handle front plate colour
127 mm
Product or component type
Contactor
tightening torque
Power circuit: 8 N.m - on screw clamp terminals - cable 25…35 mm² hexagonal screw head 4 mm
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
Power circuit: 5 N.m - on screw clamp terminals - cable 1…25 mm² hexagonal screw head 4 mm
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
[uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947
Connections - terminals
Power circuit: screw clamp terminals 1 2.5…25 mm² - cable stiffness: flexible without cable end
Power circuit: screw clamp terminals 2 2.5…16 mm² - cable stiffness: flexible without cable end
Power circuit: screw clamp terminals 1 2.5…25 mm² - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 2 2.5…10 mm² - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 1 2.5…25 mm² - cable stiffness: solid
Power circuit: screw clamp terminals 2 2.5…16 mm² - cable stiffness: solid
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid
Associated fuse rating
80 A gG at <= 690 V coordination type 1 for power circuit
80 A gG at <= 690 V coordination type 2 for power circuit
contact compatibility
M3
Control circuit voltage limits
0.1...0.3 Uc (-40…70 °C):drop-out DC
0.85...1.1 Uc (-40…55 °C):operational DC
1...1.1 Uc (55…70 °C):operational DC
width (w)
85 mm
mechanical robustness
Shocks contactor open (8 Gn for 11 ms)
Shocks contactor closed (10 Gn for 11 ms)
Vibrations contactor opened (2 Gn, 5...300 Hz)
Vibrations contactor closed (4 Gn, 5...300 Hz)
Flame retardance
V1 conforming to UL 94
Net weight
2.21 kg
time constant
75 ms
Hold-in power consumption in w
22 W at 20 °C
Mounting support
Plate
Rail
power dissipation per pole
5.4 W AC-1
depth
182 mm
inrush power in w
22 W (at 20 °C)
mechanical durability
10 Mcycles
electrical durability
1.4 Mcycles 60 A AC-1 at Ue <= 440 V
Irms rated making capacity
800 A at 440 V for power circuit conforming to IEC 60947
Pollution degree
3
Maximum operating rate
3600 cyc/h 60 °C
operating time
4...19 ms opening
12...26 ms closing
Protective cover
Without
coil technology
Built-in bidirectional peak limiting diode suppressor
Pole contact composition
2 NO + 2 NC
Poles description
4P
Utilisation category
AC-1
Safety reliability level
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Environment
ip degree of protection
IP20 front face conforming to IEC 60529
operating altitude
0...3000 m
Permissible ambient air temperature around the device
-40…60 °C
60…70 °C with derating
Range of product
TeSys Deca
overvoltage category
III
standards
CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
fire resistance
850 °C conforming to IEC 60695-2-1