[ie] rated operational current
20 A (at <50 °C) at <= 440 V AC AC-1 for power circuit
16 A (at <70 °C) at 690 V AC AC-1 for power circuit
[ue] rated operational voltage
Power circuit: 690 V AC 50/60 Hz
[ics] rated service breaking capacity
110 A at 415 V conforming to IEC 60947
110 A at 440 V conforming to IEC 60947
80 A at 500 V conforming to IEC 60947
110 A at 220...230 V conforming to IEC 60947
110 A at 380...400 V conforming to IEC 60947
70 A at 660...690 V conforming to IEC 60947
[icw] rated short-time withstand current
90 A 50 °C - 1 s for power circuit
85 A 50 °C - 5 s for power circuit
80 A 50 °C - 10 s for power circuit
60 A 50 °C - 30 s for power circuit
45 A 50 °C - 1 min for power circuit
40 A 50 °C - 3 min for power circuit
20 A 50 °C - >= 15 min for power circuit
[ith] conventional thermal current
20 A (at 50 °C) for power circuit
Product certifications
CB Scheme
CCC
UL
CSA
EAC
CE
UKCA
Handle front plate colour
58 mm
Product or component type
Contactor
tightening torque
0.8…1.3 N.m - on screw clamp terminals Philips No 2
0.8…1.3 N.m - on screw clamp terminals flat Ø 6 mm
0.8…1.3 N.m - on screw clamp terminals pozidriv No 2
[uimp] rated impulse withstand voltage
8 kV
Connections - terminals
Screw clamp terminals 1 cable(s) 1.5…4 mm²solid
Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable end
Screw clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable end
Screw clamp terminals 2 cable(s) 1.5…4 mm²solid
Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end
Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end
Associated fuse rating
25 A gG at <= 440 V for power circuit
25 A aM for power circuit
Device application
Control
Control circuit voltage limits
Operational: 0.85...1.1 Uc (at <50 °C)
Drop-out: 0.1...0.75 Uc (at <50 °C)
width (w)
45 mm
mechanical robustness
Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Flame retardance
V1 conforming to UL 94
Requirement 2 conforming to NF F 16-101
Requirement 2 conforming to NF F 16-102
Heat dissipation
3 W
Net weight
0.225 kg
Hold-in power consumption in va
3 VA (at 20 °C)
Mounting support
Rail
Plate
depth
57 mm
Inrush power in va
3 VA (at 20 °C)
mechanical durability
10 Mcycles
electrical durability
0.18 Mcycles 20 A AC-1 at Ue <= 440 V
Irms rated making capacity
110 A AC for power circuit conforming to NF C 63-110
110 A AC for power circuit conforming to IEC 60947
Maximum operating rate
3600 cyc/h
operating time
30...40 ms coil energisation and NO closing
30 ms coil de-energisation and NO opening
Power pole contact composition
4 NO
Poles description
4P
Utilisation category
AC-1
Safety reliability level
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Signalling circuit frequency
<= 400 Hz