All categories
Compare Cart

LC3D120AP7 - TeSys Deca star delta starter 3 x 3P (3 NO) 12 A 230 V AC coil - Schneider Electric

Expected in 2-4 weeks
LC3D120AP7 - TeSys Deca star delta starter 3 x 3P (3 NO) 12 A 230 V AC coil - Schneider Electric - TeSys Deca star delta starter 3 x 3P (3 NO) 12 A 230 V AC coil - Schneider Electric - 0
LC3D120AP7 - TeSys Deca star delta starter 3 x 3P (3 NO) 12 A 230 V AC coil - Schneider Electric
256,44 €
256,44 € incl. VAT
Text About:
TeSys Deca star delta starter 3 x 3P (3 NO) 12 A 230 V AC coil - Schneider Electric
256,44 €
SPECIFICATIONS
Main
Contactor application Motor control
Device short name LC3D
Interlocking type Mechanical
Range TeSys
TeSys Deca
[uc] control circuit voltage 230 V AC 50/60 Hz
Product Name TeSys Deca
[ui] rated insulation voltage Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified
Power circuit: 1000 V conforming to IEC 60947-4-1
Signalling circuit: 1000 V conforming to IEC 60947-1
Safety cover Protective cover
control circuit type AC at 50/60 Hz
motor power kW 11 kW at 380/400 V AC 50/60 Hz
11 kW at 415 V AC 50/60 Hz
11 kW at 440 V AC 50/60 Hz
5.5 kW at 220/230 V AC 50/60 Hz
Complementary
[ie] rated operational current 12 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
[ue] rated operational voltage Power circuit: <= 690 V AC 25...400 Hz
Product certifications DNV
LROS (Lloyds register of shipping)
UL
GL
RINA
BV
GOST
CCC
CSA
Handle front plate colour 124 mm
Product or component type Star delta starter
tightening torque Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
[uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947
Auxiliary contact composition 1 NC for KM1 star contactor
Connections - terminals Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end
Power circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end
Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end
Power circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end
minimum switching current 5 mA for signalling circuit
Auxiliary contacts type Mechanically linked conforming to IEC 60947-5-1 3 x 1 NO + 1 NC
Mirror contact conforming to IEC 60947-4-1 3 x 1 NC
Control circuit voltage limits Drop-out: 0.3...0.6 Uc at 50/60 Hz (at <60 °C)
Operational: 0.8...1.1 Uc at 50 Hz (at <60 °C)
Operational: 0.85...1.1 Uc at 60 Hz (at <60 °C)
width (w) 143 mm
mechanical robustness Vibrations contactor open: 2 Gn, 5...300 Hz
Vibrations contactor closed: 4 Gn, 5...300 Hz
Shocks contactor open: 10 Gn for 11 ms
Shocks contactor closed: 15 Gn for 11 ms
Flame retardance V1 conforming to UL 94
Heat dissipation 2…3 W at 50/60 Hz
Net weight 1.53 kg
Hold-in power consumption in va 7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
7 VA 50 Hz cos phi 0.3 (at 20 °C)
Mounting support Rail
depth 143 mm
Inrush power in va 70 VA 60 Hz cos phi 0.75 (at 20 °C)
70 VA 50 Hz cos phi 0.75 (at 20 °C)
mechanical durability 15 Mcycles
electrical durability 2 Mcycles 12 A AC-3 at Ue <= 440 V
Device presentation Pre-wired
Pollution degree 3
Maximum operating rate 30 cyc/h 60 °C
minimum switching voltage 17 V for signalling circuit
Power pole contact composition 3 x 3 NO
non-overlap time 1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
coil technology Without built-in suppressor module
Starting time 30 s
Poles description 3 x 3P
Utilisation category AC-3
Signalling circuit frequency 25...400 Hz
Environment
Ambient air temp for storage/transportation -60…80 °C
Climatic withstand conforming to IACS E10
conforming to IEC 60947-1 Annex Q category D
ip degree of protection IP20 front face conforming to IEC 60529
operating altitude 3000 m without derating
ambient air temperature for operation -40…70 °C at Uc
overvoltage category III
standards UL 508
EN 60947-5-1
CSA C22.2 No 14
IEC 60947-4-1
IEC 60947-5-1
EN 60947-4-1
IEC 60335-1
fire resistance 850 °C conforming to IEC 60695-2-1
protective treatment TH conforming to IEC 60068-2-30
insulation resistance > 10 MOhm for signalling circuit
Recently viewed
256,44 €
256,44 € incl. VAT
Expected in 2-4 weeks