Main
Contactor application
Resistive load
Motor control
Device short name
LC2D
Interlocking type
Mechanical
Range
TeSys
TeSys Deca
[uc] control circuit voltage
100...250 V AC 50/60 Hz
100...250 V DC
Front cover
With
Product Name
TeSys D Green
TeSys Deca
Motor power hp (ul / csa)
2 hp at 115 V AC 60 Hz for 1 phase motors
5 hp at 230/240 V AC 60 Hz for 1 phase motors
10 hp at 200/208 V AC 60 Hz for 3 phases motors
10 hp at 230/240 V AC 60 Hz for 3 phases motors
20 hp at 460/480 V AC 60 Hz for 3 phases motors
25 hp at 575/600 V AC 60 Hz for 3 phases motors
[ui] rated insulation voltage
Power circuit: 690 V conforming to IEC 60947-4-1
Signalling circuit: 690 V conforming to IEC 60947-1
control circuit type
AC at 50/60 Hz AC/DC electronic
DC AC/DC electronic
motor power kW
9 kW at 220...230 V AC 50 Hz
18.5 kW at 380...400 V AC 50 Hz
18.5 kW at 415 V AC 50 Hz
18.5 kW at 440 V AC 50 Hz
18.5 kW at 500 V AC 50 Hz
18.5 kW at 660...690 V AC 50 Hz
average impedance
2 mOhm - Ith 50 A 50 Hz for power circuit
Complementary
[ie] rated operational current
50 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
38 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
[ue] rated operational voltage
Power circuit: <= 690 V AC 25...400 Hz
[ics] rated service breaking capacity
550 A at 440 V for power circuit conforming to IEC 60947
[icw] rated short-time withstand current
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
430 A 40 °C - 1 s for power circuit
60 A 40 °C - 10 min for power circuit
150 A 40 °C - 1 min for power circuit
310 A 40 °C - 10 s for power circuit
[ith] conventional thermal current
10 A (at 60 °C) for signalling circuit
50 A (at 60 °C) for power circuit
Product certifications
CCC
CSA
EAC
UL
KC
DNV-GL
LROS (Lloyds register of shipping)
UKCA
Handle front plate colour
85 mm
Product or component type
Reversing contactor
tightening torque
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver Philips No 2
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
[uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947
Auxiliary contact composition
1 NO + 1 NC
Connections - terminals
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid
Power circuit: screw clamp terminals 1 cable(s) 2.5…10 mm²flexible without cable end
Power circuit: screw clamp terminals 2 cable(s) 2.5…10 mm²flexible without cable end
Power circuit: screw clamp terminals 1 cable(s) 1…10 mm²flexible with cable end
Power circuit: screw clamp terminals 2 cable(s) 1.5…6 mm²flexible with cable end
Power circuit: screw clamp terminals 1 cable(s) 1.5…10 mm²solid
Power circuit: screw clamp terminals 2 cable(s) 2.5…10 mm²solid
minimum switching current
5 mA for signalling circuit
Associated fuse rating
10 A gG for signalling circuit conforming to IEC 60947-5-1
63 A gG at <= 690 V coordination type 1 for power circuit
63 A gG at <= 690 V coordination type 2 for power circuit
Auxiliary contacts type
type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
type mirror contact 1 NC conforming to IEC 60947-4-1
Control circuit voltage limits
<= 0.1 Uc (-40…70 °C):drop-out AC/DC
0.85...1.1 Uc (-40…60 °C):operational AC/DC
1...1.1 Uc (60…70 °C):operational AC/DC
width (w)
90 mm
mechanical robustness
Vibrations contactor open: 2 Gn, 5...300 Hz
Vibrations contactor closed: 4 Gn, 5...300 Hz
Shocks contactor closed: 15 Gn for 11 ms
Shocks contactor open: 8 Gn for 11 ms
Colour
Grey (SE GREY 6)
Green (SE GREEN 2)
Flame retardance
V1 conforming to UL 94
Heat dissipation
1.1 W at 50/60 Hz
Net weight
0.933 kg
Hold-in power consumption in va
1.6 VA (at 20 °C) 50/60 Hz
Hold-in power consumption in w
1.1 W at 20 °C
Mounting support
Rail
Plate
power dissipation per pole
5 W AC-1
3 W AC-3
depth
92 mm
Inrush power in va
25 VA 50/60 Hz (at 20 °C)
inrush power in w
18 W at 20 °C
mechanical durability
15 Mcycles
electrical durability
1.8 Mcycles 35 A AC-3 at Ue <= 440 V
0.9 Mcycles 50 A AC-1 at Ue <= 440 V
Device presentation
Preassembled with reversing power busbar
Irms rated making capacity
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
550 A at 440 V for power circuit conforming to IEC 60947
Pollution degree
3
Maximum operating rate
3600 cyc/h 60 °C
operating time
45...55 ms closing
20...90 ms opening
minimum switching voltage
17 V for signalling circuit
Power pole contact composition
3 NO
non-overlap time
1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
coil technology
Built-in bidirectional peak limiting
Poles description
3P
Utilisation category
AC-3
AC-1
Safety reliability level
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Signalling circuit frequency
25...400 Hz
Environment
Ambient air temp for storage/transportation
-60…80 °C
Climatic withstand
conforming to IACS E10
conforming to IEC 60947-1 Annex Q category D
ip degree of protection
IP20 front face conforming to IEC 60529
operating altitude
0...3000 m
ambient air temperature for operation
-40…60 °C
60…70 °C with derating
overvoltage category
III
standards
EN/IEC 60947-4-1
EN/IEC 60947-5-1
UL 60947-4-1
CSA C22.2 No 60947-4-1
IEC 60335-1
fire resistance
850 °C conforming to IEC 60695-2-1
protective treatment
TH conforming to IEC 60068-2-30
insulation resistance
> 10 MOhm for signalling circuit