Main
Contactor application
Resistive load
Motor control
Device short name
LC1F
Range
TeSys
[uc] control circuit voltage
230 V AC 40...400 Hz
[ui] rated insulation voltage
1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 group C
control circuit type
AC at 40...400 Hz
motor power kW
450 kW at 1000 V AC 50/60 Hz (AC-3)
400 kW at 380...400 V AC 50/60 Hz (AC-3)
425 kW at 415 V AC 50/60 Hz (AC-3)
425 kW at 440 V AC 50/60 Hz (AC-3)
450 kW at 500 V AC 50/60 Hz (AC-3)
475 kW at 660...690 V AC 50/60 Hz (AC-3)
220 kW at 220...230 V AC 50/60 Hz (AC-3)
110 kW at 400 V AC 50/60 Hz (AC-4)
average impedance
0.1 mOhm - Ith 1600 A 50 Hz
Complementary
[ie] rated operational current
1600 A (at <40 °C) at <= 440 V AC AC-1
780 A (at <55 °C) at <= 440 V AC AC-3
[ue] rated operational voltage
<= 1000 V AC 50/60 Hz
<= 460 V DC
compatibility code
LC1F
[ics] rated service breaking capacity
6240 A conforming to IEC 60947-4-1
[icw] rated short-time withstand current
3000 A 40 °C - 3 min
6250 A 40 °C - 10 s
5600 A 40 °C - 30 s
4600 A 40 °C - 1 min
2200 A 40 °C - 10 min
[ith] conventional thermal current
1600 A (at 40 °C)
Product certifications
CSA
RMRoS
BV
UL
DNV
LROS (Lloyds register of shipping)
CB
RINA
ABS
Handle front plate colour
434 mm
Product or component type
Contactor
tightening torque
Control circuit: 1.2 N.m
Power circuit: 58 N.m
[uimp] rated impulse withstand voltage
8 kV
Connections - terminals
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Power circuit: bar 2 cable(s) - busbar cross section: 100 x 5 mm
Power circuit: bolted connection
Associated fuse rating
1600 A gG at <= 440 V
800 A aM at <= 440 V
Control circuit voltage limits
Operational: 0.85...1.1 Uc 40...400 Hz (at 55 °C)
Drop-out: 0.2...0.4 Uc 40...400 Hz (at 55 °C)
width (w)
702 mm
Heat dissipation
44 W
Net weight
39.5 kg
Hold-in power consumption in va
50 VA, 40...400 Hz cos phi 0.9 (at 20 °C)
Mounting support
Plate
power dissipation per pole
250 W AC-1
60 W AC-3
depth
255 mm
Inrush power in va
2100 VA, 40...400 Hz cos phi 0.9 (at 20 °C)
mechanical durability
5 Mcycles
Maximum operating rate
600 cyc/h 55 °C
operating time
40...80 ms closing
130...230 ms opening
contactor coil voltage
230 V AC standard
Motor power range
250…500 kW at 380…440 V 3 phases
110…220 kW at 200…240 V 3 phases
250…500 kW at 480…500 V 3 phases
Power pole contact composition
3 NO
motor starter type
Direct on-line contactor
Poles description
3P
Utilisation category
AC-1
AC-4
AC-3
Environment
Ambient air temp for storage/transportation
-60…80 °C
ip degree of protection
IP20 front face with shrouds conforming to IEC 60529
IP20 front face with shrouds conforming to VDE 0106
operating altitude
3000 m without derating
Permissible ambient air temperature around the device
-40…70 °C
Range of product
TeSys F
ambient air temperature for operation
-5…55 °C
overvoltage category
III
standards
JIS C8201-4-1
EN 60947-1
IEC 60947-1
IEC 60947-4-1
EN 60947-4-1
protective treatment
TH