Contactor application
Resistive load
Motor control
Device short name
LC1F
Range
TeSys
[uc] control circuit voltage
48...1000 V AC 40...400 Hz with LX1/LX9 coil
48...440 V DC with LX4 coil
Product Name
TeSys F
[ui] rated insulation voltage
1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 group C
motor power kW
335 kW at 380...400 V AC 50/60 Hz (AC-3)
375 kW at 415 V AC 50/60 Hz (AC-3)
400 kW at 440 V AC 50/60 Hz (AC-3)
400 kW at 500 V AC 50/60 Hz (AC-3)
450 kW at 1000 V AC 50/60 Hz (AC-3)
200 kW at 220...240 V AC 50/60 Hz (AC-3)
450 kW at 660...690 V AC 50/60 Hz (AC-3)
100 kW at 400 V AC 50/60 Hz (AC-4)
average impedance
0.12 mOhm - Ith 1000 A 50 Hz
Complementary
[ie] rated operational current
1000 A (at <40 °C) at <= 440 V AC AC-1
630 A (at <55 °C) at <= 440 V AC AC-3
[ue] rated operational voltage
<= 1000 V AC 50/60 Hz
<= 460 V DC
compatibility code
LC1F
[ics] rated service breaking capacity
5040 A conforming to IEC 60947-4-1
[icw] rated short-time withstand current
5050 A 40 °C - 10 s
4400 A 40 °C - 30 s
3400 A 40 °C - 1 min
2200 A 40 °C - 3 min
1600 A 40 °C - 10 min
[ith] conventional thermal current
1000 A (at 40 °C)
1250 A
Product certifications
ABS
UL
RINA
DNV
CSA
CB
LROS (Lloyds register of shipping)
BV
RMRoS
UKCA
Handle front plate colour
304 mm
Product or component type
Contactor
tightening torque
Power circuit: 58 N.m
Control circuit: 1.2 N.m
[uimp] rated impulse withstand voltage
8 kV
Connections - terminals
Power circuit: bar 2 cable(s) - busbar cross section: 60 x 5 mm
Power circuit: bolted connection
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²solid without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²
Associated fuse rating
630 A aM at <= 440 V
1000 A gG at <= 440 V
Control circuit voltage limits
Operational: 0.85...1.1 Uc AC 40...400 Hz with LX1/LX9 coil
Drop-out: 0.25...0.5 Uc AC 40...400 Hz with LX1/LX9 coil
Operational: 0.85...1.1 Uc DC with LX4 coil
Drop-out: 0.2...0.35 Uc DC with LX4 coil
width (w)
309 mm
mechanical robustness
Vibrations contactor open: 2 Gn, 5...300 Hz
Vibrations contactor closed: 4 Gn, 5...300 Hz
Shocks contactor open: 6 Gn for 1/2 sine wave (11 ms)
Shocks contactor closed: 15 Gn for 1/2 sine wave (11 ms)
Heat dissipation
20 W
Net weight
18.6 kg
Hold-in power consumption in va
20…25 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil
6.5…12.5 VA (at 20 °C)with LX4 coil
Mounting support
Plate
power dissipation per pole
120 W AC-1
48 W AC-3
depth
255 mm
Inrush power in va
1500…1730 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil
1420…1920 VA (at 20 °C)with LX4 coil
mechanical durability
5 Mcycles
Irms rated making capacity
6300 A AC conforming to IEC 60947-4-1
Maximum operating rate
1200 cyc/h 55 °C
operating time
40...80 ms closing for with LX1/LX9 coil
100...200 ms opening for with LX1/LX9 coil
60...70 ms closing for with LX4 coil
40...50 ms opening for with LX4 coil
Power pole contact composition
3 NO
Poles description
3P
Utilisation category
AC-4
AC-1
AC-3
Environment
Ambient air temp for storage/transportation
-60…80 °C
ip degree of protection
IP20 front face with shrouds conforming to IEC 60529
IP20 front face with shrouds conforming to VDE 0106
operating altitude
3000 m without derating
Permissible ambient air temperature around the device
-40…70 °C
ambient air temperature for operation
-5…55 °C
overvoltage category
III
standards
EN 60947-4-1
IEC 60947-4-1
IEC 60947-1
JIS C8201-4-1
EN 60947-1
protective treatment
TH