Main
Contactor application
Motor control
Resistive load
Device short name
LC1F
Range
TeSys
[uc] control circuit voltage
230 V AC 40...400 Hz
[ui] rated insulation voltage
1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 group C
control circuit type
AC at 40...400 Hz
motor power kW
250 kW at 380...400 V AC 50/60 Hz (AC-3)
280 kW at 415 V AC 50/60 Hz (AC-3)
295 kW at 440 V AC 50/60 Hz (AC-3)
355 kW at 500 V AC 50/60 Hz (AC-3)
335 kW at 660...690 V AC 50/60 Hz (AC-3)
335 kW at 1000 V AC 50/60 Hz (AC-3)
147 kW at 220...230 V AC 50/60 Hz (AC-3)
80 kW at 400 V AC 50/60 Hz (AC-4)
average impedance
0.18 mOhm - Ith 700 A 50 Hz
Complementary
[ie] rated operational current
700 A (at <40 °C) at <= 440 V AC AC-1
500 A (at <55 °C) at <= 440 V AC AC-3
[ue] rated operational voltage
<= 690 V AC 50/60 Hz
<= 460 V DC
compatibility code
LC1F
[ics] rated service breaking capacity
4000 A conforming to IEC 60947-4-1
[icw] rated short-time withstand current
4200 A 40 °C - 10 s
3200 A 40 °C - 30 s
2400 A 40 °C - 1 min
1500 A 40 °C - 3 min
1200 A 40 °C - 10 min
[ith] conventional thermal current
700 A (at 40 °C)
Product certifications
DNV
RINA
RMRoS
ABS
UL
CSA
BV
CB
LROS (Lloyds register of shipping)
UKCA
Handle front plate colour
238 mm
Product or component type
Contactor
tightening torque
Control circuit: 1.2 N.m
Power circuit: 35 N.m
[uimp] rated impulse withstand voltage
8 kV
Connections - terminals
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Power circuit: bar 2 cable(s) - busbar cross section: 40 x 5 mm
Power circuit: lugs-ring terminals 2 cable(s) 240 mm²
Power circuit: bolted connection
Associated fuse rating
500 A aM at <= 440 V
800 A gG at <= 440 V
Control circuit voltage limits
Operational: 0.85...1.1 Uc 40...400 Hz (at 55 °C)
Drop-out: 0.3...0.5 Uc 40...400 Hz (at 55 °C)
width (w)
233 mm
Heat dissipation
18 W
Net weight
11.35 kg
Hold-in power consumption in va
18 VA, 40...400 Hz cos phi 0.9 (at 20 °C)
Mounting support
Plate
power dissipation per pole
88 W AC-1
45 W AC-3
depth
232 mm
Inrush power in va
1100 VA, 40...400 Hz cos phi 0.9 (at 20 °C)
mechanical durability
10 Mcycles
Maximum operating rate
2400 cyc/h 55 °C
operating time
40...65 ms closing
100...170 ms opening
contactor coil voltage
230 V AC standard
Motor power range
250…500 kW at 380…440 V 3 phases
110…220 kW at 380…440 V 3 phases
110…220 kW at 200…240 V 3 phases
250…500 kW at 480…500 V 3 phases
Power pole contact composition
3 NO
motor starter type
Direct on-line contactor
Poles description
3P
Utilisation category
AC-1
AC-4
AC-3
Environment
Ambient air temp for storage/transportation
-60…80 °C
ip degree of protection
IP20 front face with shrouds conforming to IEC 60529
IP20 front face with shrouds conforming to VDE 0106
operating altitude
3000 m without derating
Permissible ambient air temperature around the device
-40…70 °C
Range of product
TeSys F
ambient air temperature for operation
-5…55 °C
overvoltage category
III
standards
IEC 60947-4-1
JIS C8201-4-1
EN 60947-1
IEC 60947-1
EN 60947-4-1
protective treatment
TH