Main
Contactor application
Motor control
Resistive load
Device short name
LC1F
Range
TeSys
[uc] control circuit voltage
24...1000 V AC 40...400 Hz with LX1/LX9 coil
24...460 V DC with LX4 coil
100...250 V AC 50/60 Hz with LXE coil
100...380 V DC with LXE coil
Product Name
TeSys F
[ui] rated insulation voltage
1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 group C
motor power kW
160 kW at 1000 V AC 50/60 Hz (AC-3)
160 kW at 380...400 V AC 50/60 Hz (AC-3)
180 kW at 415 V AC 50/60 Hz (AC-3)
200 kW at 440 V AC 50/60 Hz (AC-3)
200 kW at 500 V AC 50/60 Hz (AC-3)
100 kW at 220...240 V AC 50/60 Hz (AC-3)
220 kW at 660...690 V AC 50/60 Hz (AC-3)
59 kW at 400 V AC 50/60 Hz (AC-4)
average impedance
0.28 mOhm - Ith 400 A 50 Hz
Complementary
[ie] rated operational current
400 A (at <40 °C) at <= 440 V AC AC-1
330 A (at <55 °C) at <= 440 V AC AC-3
[ue] rated operational voltage
<= 1000 V AC 50/60 Hz
<= 460 V DC
compatibility code
LC1F
[ics] rated service breaking capacity
2640 A conforming to IEC 60947-4-1
[icw] rated short-time withstand current
2650 A 40 °C - 10 s
1800 A 40 °C - 30 s
1300 A 40 °C - 1 min
900 A 40 °C - 3 min
750 A 40 °C - 10 min
[ith] conventional thermal current
400 A (at 40 °C)
Product certifications
ABS
CSA
UL
RMRoS
DNV
CB
BV
LROS (Lloyds register of shipping)
RINA
UKCA
Handle front plate colour
206 mm
Product or component type
Contactor
tightening torque
Power circuit: 35 N.m
Control circuit: 1.2 N.m
Control circuit: 0.6 N.m
[uimp] rated impulse withstand voltage
8 kV
Connections - terminals
Power circuit: lugs-ring terminals 1 cable(s) 240 mm²
Power circuit: bar 2 cable(s) - busbar cross section: 30 x 5 mm
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²solid without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²
Control circuit: screw clamp terminals 1.0 cable(s) 0.2…2.5 mm²flexible without cable end
Control circuit: screw clamp terminals 1.0 cable(s) 0.25…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1.0 cable(s) 0.2…2.5 mm²solid without cable end
Associated fuse rating
400 A aM at <= 440 V
500 A gG at <= 440 V
Control circuit voltage limits
Operational: 0.85...1.1 Uc AC 40...400 Hz with LX1/LX9 coil
Drop-out: 0.35...0.55 Uc AC 40...400 Hz with LX1/LX9 coil
Operational: 0.85...1.1 Uc DC with LX4 coil
Drop-out: 0.15...0.2 Uc DC with LX4 coil
Operational: 85...275 V AC 50/60 Hz with LXE coil
Drop-out: 0...60 V AC 50/60 Hz with LXE coil
Operational: 85...418 V DC with LXE coil
Drop-out: 0...45 V DC with LXE coil
width (w)
213 mm
mechanical robustness
Vibrations contactor open: 2 Gn, 5...300 Hz
Vibrations contactor closed: 5 Gn, 5...300 Hz
Shocks contactor open: 6 Gn for 1/2 sine wave (11 ms)
Shocks contactor closed: 15 Gn for 1/2 sine wave (11 ms)
Heat dissipation
8 W
2.2…5.5 W
Net weight
9.5 kg
Hold-in power consumption in va
8…10 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil
3.68…4.53 VA (at 20 °C)with LX4 coil
4.5…7.0 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil
2.5…4.0 VA (at 20 °C)with LXE coil
Mounting support
Plate
power dissipation per pole
44 W AC-1
31 W AC-3
depth
219 mm
Inrush power in va
600…700 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil
655…803 VA (at 20 °C)with LX4 coil
300…350 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil
300…310 VA (at 20 °C)with LXE coil
mechanical durability
10 Mcycles
Irms rated making capacity
3300 A AC conforming to IEC 60947-4-1
Maximum operating rate
2400 cyc/h 55 °C
operating time
40...65 ms closing for with LX1/LX9 coil
100...170 ms opening for with LX1/LX9 coil
40...50 ms closing for with LX4 coil
40...65 ms opening for with LX4 coil
40...80 ms closing for with LXE coil
6...54 ms opening for with LXE coil
Power pole contact composition
3 NO
Poles description
3P
Utilisation category
AC-4
AC-3
AC-1
Environment
Ambient air temp for storage/transportation
-60…80 °C
ip degree of protection
IP20 front face with shrouds conforming to IEC 60529
IP20 front face with shrouds conforming to VDE 0106
operating altitude
3000 m without derating
Permissible ambient air temperature around the device
-40…70 °C
ambient air temperature for operation
-5…55 °C
overvoltage category
III
standards
IEC 60947-4-1
JIS C8201-4-1
EN 60947-1
IEC 60947-1
EN 60947-4-1
protective treatment
TH