Main
Contactor application
Motor control
Resistive load
Device short name
LC1F
Range
TeSys
[uc] control circuit voltage
24 V AC 40...400 Hz
[ui] rated insulation voltage
1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 group C
control circuit type
AC at 40...400 Hz
motor power kW
132 kW at 380...400 V AC 50/60 Hz (AC-3)
140 kW at 415 V AC 50/60 Hz (AC-3)
140 kW at 440 V AC 50/60 Hz (AC-3)
160 kW at 500 V AC 50/60 Hz (AC-3)
160 kW at 660...690 V AC 50/60 Hz (AC-3)
147 kW at 1000 V AC 50/60 Hz (AC-3)
75 kW at 220...230 V AC 50/60 Hz (AC-3)
51 kW at 400 V AC 50/60 Hz (AC-4)
average impedance
0.3 mOhm - Ith 350 A 50 Hz
Complementary
[ie] rated operational current
350 A (at <40 °C) at <= 440 V AC AC-1
265 A (at <55 °C) at <= 440 V AC AC-3
[ue] rated operational voltage
<= 1000 V AC-1
<= 690 V AC-3
<= 690 V AC-4
<= 460 V DC
compatibility code
LC1F
[ics] rated service breaking capacity
2120 A conforming to IEC 60947-4-1
[icw] rated short-time withstand current
2200 A 40 °C - 10 s
1230 A 40 °C - 30 s
950 A 40 °C - 1 min
620 A 40 °C - 3 min
480 A 40 °C - 10 min
[ith] conventional thermal current
350 A (at 40 °C)
Product certifications
RINA
BV
CB
RMRoS
UL
ABS
CCC
LROS (Lloyds register of shipping)
DNV
UKCA
Handle front plate colour
203 mm
Product or component type
Contactor
tightening torque
Control circuit: 1.2 N.m
Power circuit: 35 N.m
[uimp] rated impulse withstand voltage
8 kV
Connections - terminals
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Power circuit: bar 2 cable(s) - busbar cross section: 32 x 4 mm
Power circuit: lugs-ring terminals 1 cable(s) 240 mm²
Power circuit: connector 1 cable(s) 240 mm²
Power circuit: bolted connection
Associated fuse rating
315 A aM at <= 440 V
400 A gG at <= 440 V
Control circuit voltage limits
Operational: 0.85...1.1 Uc 40...400 Hz (at 55 °C)
Drop-out: 0.15...0.2 Uc 40...400 Hz (at 55 °C)
width (w)
201.5 mm
Heat dissipation
8 W
Net weight
7.44 kg
Hold-in power consumption in va
10 VA, 40...400 Hz cos phi 0.9 (at 20 °C)
Mounting support
Plate
power dissipation per pole
37 W AC-1
21 W AC-3
depth
213 mm
Inrush power in va
650 VA, 40...400 Hz cos phi 0.9 (at 20 °C)
mechanical durability
10 Mcycles
Maximum operating rate
2400 cyc/h 55 °C
operating time
40...65 ms closing
100...170 ms opening
Power pole contact composition
3 NO
Poles description
3P
Utilisation category
AC-1
AC-4
AC-3
Environment
Ambient air temp for storage/transportation
-60…80 °C
ip degree of protection
IP20 front face with shrouds conforming to IEC 60529
IP20 front face with shrouds conforming to VDE 0106
operating altitude
3000 m without derating
Permissible ambient air temperature around the device
-40…70 °C
Range of product
TeSys F
ambient air temperature for operation
-5…55 °C
overvoltage category
III
standards
IEC 60947-4-1
EN 60947-1
JIS C8201-4-1
IEC 60947-1
EN 60947-4-1
protective treatment
TH