SPECIFICATIONS
Main
Contactor application Resistive load
Motor control
Device short name LC1F
Range TeSys
[uc] control circuit voltage 220 V DC
[ui] rated insulation voltage 1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 group C
control circuit type DC standard
motor power kW 90 kW at 380...400 V AC 50/60 Hz (AC-3)
100 kW at 415 V AC 50/60 Hz (AC-3)
100 kW at 440 V AC 50/60 Hz (AC-3)
110 kW at 500 V AC 50/60 Hz (AC-3)
110 kW at 660...690 V AC 50/60 Hz (AC-3)
55 kW at 220...230 V AC 50/60 Hz (AC-3)
33 kW at 400 V AC 50/60 Hz (AC-4)
average impedance 0.33 mOhm - Ith 275 A 50 Hz
Complementary
[ie] rated operational current 275 A (at <40 °C) at <= 440 V AC-1
185 A (at <55 °C) at <= 440 V AC-3
[ue] rated operational voltage <= 460 V DC
<= 690 V AC 50/60 Hz
compatibility code LC1F
[ics] rated service breaking capacity 1480 A conforming to IEC 60947-4-1
[icw] rated short-time withstand current 1500 A 40 °C - 10 s
920 A 40 °C - 30 s
740 A 40 °C - 1 min
500 A 40 °C - 3 min
400 A 40 °C - 10 min
[ith] conventional thermal current 275 A (at 40 °C)
Product certifications UL
RINA
BV
ABS
RMRoS
CB
CSA
LROS (Lloyds register of shipping)
DNV
UKCA
Handle front plate colour 174 mm
Product or component type Contactor
tightening torque Control circuit: 1.2 N.m
Power circuit: 18 N.m
[uimp] rated impulse withstand voltage 8 kV
Connections - terminals Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Power circuit: bar 2 cable(s) - busbar cross section: 25 x 3 mm
Power circuit: lugs-ring terminals 1 cable(s) 150 mm²
Power circuit: connector 1 cable(s) 150 mm²
Power circuit: bolted connection
Associated fuse rating 200 A aM at <= 440 V
315 A gG at <= 440 V
Control circuit voltage limits Operational: 0.85...1.1 Uc (at 55 °C)
Drop-out: 0.15...0.2 Uc (at 55 °C)
width (w) 168.5 mm
Heat dissipation 5 W
Net weight 4.65 kg
Hold-in power consumption in w 5 W at 20 °C
Mounting support Plate
power dissipation per pole 12 W AC-3
25 W AC-1
depth 181 mm
inrush power in w 800 W (at 20 °C)
mechanical durability 10 Mcycles
Maximum operating rate 2400 cyc/h 55 °C
operating time 30...40 ms closing
30...50 ms opening
contactor coil voltage 220 V DC standard
Motor power range 30…50 kW at 200…240 V 3 phases
55…100 kW at 200…240 V 3 phases
55…100 kW at 380…440 V 3 phases
55…100 kW at 480…500 V 3 phases
110…220 kW at 480…500 V 3 phases
Power pole contact composition 3 NO
motor starter type Direct on-line contactor
Poles description 3P
Utilisation category AC-1
AC-4
AC-3
Environment
Ambient air temp for storage/transportation -60…80 °C
ip degree of protection IP2X front face with shrouds conforming to IEC 60529
IP2X front face with shrouds conforming to VDE 0106
operating altitude 3000 m without derating
Permissible ambient air temperature around the device -40…70 °C
Range of product TeSys F
ambient air temperature for operation -5…55 °C
overvoltage category III
standards EN 60947-1
EN 60947-4-1
IEC 60947-1
IEC 60947-4-1
JIS C8201-4-1
protective treatment TH